All categories
Compare Cart

C10B3TM025 - Circuit breaker, ComPacT NSX100B, 25kA/415VAC, 3 poles, TMD trip unit 25A - Schneider Electric

Expected in 2-4 weeks EAN: 3606481996145
C10B3TM025 - Circuit breaker, ComPacT NSX100B, 25kA/415VAC, 3 poles, TMD trip unit 25A - Schneider Electric - Circuit breaker, ComPacT NSX100B, 25kA/415VAC, 3 poles, TMD trip unit 25A - Schneider Electric - 0
EAN: 3606481996145
C10B3TM025 - Circuit breaker, ComPacT NSX100B, 25kA/415VAC, 3 poles, TMD trip unit 25A - Schneider Electric
160,34 €
160,34 € incl. VAT
Text About:
Circuit breaker, ComPacT NSX100B, 25kA/415VAC, 3 poles, TMD trip unit 25A - Schneider Electric
160,34 €
SPECIFICATIONS
Main
Range ComPacT nouvelle génération
sectioning ability Oui se conformer à EN/CEI 60947-2
job category Catégorie A
name of the device NSX100B
type of product or equipment Disjoncteur
Product Name ComPacT NSX nouvelle génération
[ui] rated insulation voltage 800 V CA 50/60 Hz
trigger protection functions LI
circuit breaker installation mode Fixe
performance level B 25 kA 415 V CA
trigger name TM-D
type of trigger Thermique-magnétique
ultimate short-circuit breaking capacity [icu] 40 kA Icu à 220/240 V CA 50/60 Hz se conformer à CEI 60947-2
25 kA Icu à 380/415 V CA 50/60 Hz se conformer à CEI 60947-2
20 kA Icu à 440 V CA 50/60 Hz se conformer à CEI 60947-2
15 kA Icu à 500 V CA 50/60 Hz se conformer à CEI 60947-2
protected poles 3d
Complementary
"no" connection 35 mm
[in] rated operational current 25 A à 40 °C
[ue] rated operational voltage 690 V CA 50/60 Hz
application Distribution
[ics] rated service breaking capacity 40 kA à 220/240 V CA 50/60 Hz se conformer à CEI 60947-2
25 kA à 380/415 V CA 50/60 Hz se conformer à CEI 60947-2
20 kA à 440 V CA 50/60 Hz se conformer à CEI 60947-2
7 kA à 500 V CA 50/60 Hz se conformer à CEI 60947-2
Handle front plate colour 161 mm
trigger caliber 25 A à 40 °C
[uimp] rated impulse withstand voltage 8 kV
product weight 2,05 kg
electrical life 50000 cycle à 440 V In/2
30000 cycle à 440 V In
20000 cycle à 690 V In/2
10000 cycle à 690 V In
mechanical endurance 50000 cycle
width (w) 105 mm
network frequency 50/60 Hz
long time protection time delay setting range [tr] 120…400 s à 1,5 x In
15 s à 6 x Ir
setting range of the long-time protection threshold [ir] (thermal protection) 0,7 à 1 x In
upstream connection Façade
downstream connection Façade
instantaneous protection threshold setting range [ii] (short-circuit protection) 300 A
number of slots for electrical auxiliaries 5 slot(s)
mounting bracket Plaque arrière
depth (p) 86 mm
Network type CA
differential protection Sans
mounting position Horizontal et vertical
Flat on the back
power loss per pole 4,01 W
tr long time protection time delay setting Fixe
instantaneous protection sensor setting ii (short circuit protection) Fixe
ir long time protection sensor setting (thermal protection) Réglable
order type Par maneton
kind of protection L : for protection surcharge (thermique)
I : for protection (magnétique) court-circuit
Poles description 3P
Environment
degree of pollution 3 se conformer à CEI 60664-1
ip degree of protection IP40 se conformer à CEI 60529
operating altitude 0...2000 m sans réduction de courant
2000 m...5000 m avec réduction de courant
product certificates CCC
EAC
Marine
class of protection against electric shock Classe II
operating ambient temperature -25…70 °C
overvoltage category Classe II
standards EN/CEI 60947
relative humidity 0…95 %
shock resistance ik IK07 se conformer à CEI 62262
storage room temperature -50…85 °C
Recently viewed
160,34 €
160,34 € incl. VAT
Expected in 2-4 weeks