All categories
Compare Cart

C104MG063 - Trip unit TM63G, ComPacT NSX100/160, 4 poles 4D (neutral fully protected), thermal magnetic protections, generator, 63A - Schneider Electric

Expected in 2-4 weeks EAN: 3606482000704
C104MG063 - Trip unit TM63G, ComPacT NSX100/160, 4 poles 4D (neutral fully protected), thermal magnetic protections, generator, 63A - Schneider Electric - Trip unit TM63G, ComPacT NSX100/160, 4 poles 4D (neutral fully protected), thermal magnetic protections, generator, 63A - Schneider Electric - 0
EAN: 3606482000704
C104MG063 - Trip unit TM63G, ComPacT NSX100/160, 4 poles 4D (neutral fully protected), thermal magnetic protections, generator, 63A - Schneider Electric
95,13 € excl. VAT
116,06 € incl. VAT
Text About:
Trip unit TM63G, ComPacT NSX100/160, 4 poles 4D (neutral fully protected), thermal magnetic protections, generator, 63A - Schneider Electric
116,06 €
SPECIFICATIONS
Main
product range ComPacT NSX100...250 nouvelle génération
ComPacT NSX100...250 DC nouvelle génération
Range ComPacT nouvelle génération
type of product or equipment Déclencheur
trigger protection functions LI
circuit breaker installation mode Fixe
neutral pole position Gauche
trigger name TM-G
type of trigger Thermique-magnétique
protected poles 4d
Complementary
[ue] rated operational voltage 690 V CA 50/60 Hz
750 V CC
application Générateur
range compatibility ComPacT nouvelle génération NSX100
ComPacT nouvelle génération NSX160
ComPacT nouvelle génération NSX100 CC
trigger caliber 63 A à 40 °C
network frequency 50/60 Hz
long time protection time delay setting range [tr] 120…400 s à 1,5 x In
setting range of the long-time protection threshold [ir] (thermal protection) 0,7 à 1 x In
instantaneous protection threshold setting range [ii] (short-circuit protection) 125 A
neutral protection setting 1 x Ir (4d)
Network type CC
CA
differential protection Sans
tr long time protection time delay setting Fixe
instantaneous protection sensor setting ii (short circuit protection) Fixe
ir long time protection sensor setting (thermal protection) Réglable
kind of protection L : for protection surcharge (thermique)
I : for protection (magnétique) court-circuit
Poles description 4P
Environment
degree of pollution 3 se conformer à CEI 60947-1
ip degree of protection IP40 se conformer à CEI 60529
class of protection against electric shock Classe II
operating ambient temperature -25…70 °C
standards EN/CEI 60947-2
storage room temperature -50…85 °C
Recently viewed
95,13 € excl. VAT
116,06 € incl. VAT
Expected in 2-4 weeks