Main
																					
												(in) rated current up to 65 °c
												800 A at 50 °C
											
                            
																					
												Range
												ComPacT
											
                            
																					
												[icu] rated ultimate short-circuit breaking capacity
												85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
											
                            
																					
												Protected poles description
												3D
											
                            
																					
												Product Name
												ComPacT NS new generation
											
                            
																					
												Trip unit name
												MicroLogic 6.0
											
                            
																					
												Trip unit technology
												Electronic
											
                            
																					
												Trip unit rating
												800 A at 50 °C
											
                            
																					
												[ui] rated insulation voltage
												800 V AC 50/60 Hz conforming to IEC 60947-2
											
                            
																					
												number of poles
												3P
											
                            
																					
												Trip unit protection functions
												LSIG
											
                            
																					
												performance level
												N 50 kA 415 V AC
											
                            
																			 
																	
										Complementary
																					
												[ics] rated service short-circuit breaking capacity
												50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
											
                            
																					
												[ue] rated operational voltage
												690 V AC 50/60 Hz
											
                            
																					
												[icw] rated short-time withstand current
												19.2 kA 1 s conforming to IEC 60947-2
											
                            
																					
												Control type
												Manually operated
											
                            
																					
												depth (d)
												147 mm
											
                            
																					
												Product certifications
												IECEE CB Scheme
											
                            
																					
												[ig] ground-fault protection pick-up adjustment range
												0.3...1 x In for In <= 400 A
0.2...1 x In for 400 A < In < 1250 A
500...1200 A for In >= 1250 A
											
                            
																					
												[ii] instantaneous protection pick-up adjustment range
												Off
2...15 x In
											
                            
																					
												[ir] long-time protection pick-up adjustment range
												0.4...1 x In
											
                            
																					
												Connection pitch
												70 mm
											
                            
																					
												Product or component type
												Circuit breaker
											
                            
																					
												[isd] short-time protection pick-up adjustment range
												1.5...10 x Ir
											
                            
																					
												[uimp] rated impulse withstand voltage
												8 kV conforming to IEC 60947-2
											
                            
																					
												Auxiliary contact composition
												1 NO/NC
											
                            
																					
												[tg] ground-fault protection time delay adjustment range
												0.1…0.4 s I²t=on
0…0.4 s I²t=off
											
                            
																					
												height (h)
												327 mm
											
                            
																					
												[tr] long-time protection delay adjustment range
												12.5…600 s at 1.5 x Ir
0.5…24 s at 6 x Ir
0.7…16.6 s at 7.2 x Ir
											
                            
																					
												[tsd] short-time protection delay adjustment range
												0.1…0.4 s I²t=on
0…0.4 s I²t=off
											
                            
																					
												Device application
												Distribution
											
                            
																					
												ground-fault protection pick-up adjustment type ig
												Adjustable 9 settings
											
                            
																					
												ground-fault protection time delay adjustment type tg
												Adjustable
											
                            
																					
												width (w)
												210 mm
											
                            
																					
												network frequency
												50/60 Hz
											
                            
																					
												thermal memory
												20 mn
											
                            
																					
												Ik degree of protection
												IK07 conforming to EN 50102
											
                            
																					
												Local signalling
												4 LEDs (red) for fault indication
1 LED (yellow) for overload
											
                            
																					
												Mounting mode
												Fixed
											
                            
																					
												power losses
												15 W
											
                            
																					
												long-time pick-up adjustment type ir (thermal protection)
												Adjustable 9 settings
											
                            
																					
												Net weight
												14 kg
											
                            
																					
												long-time protection delay adjustment type tr
												Adjustable 9 settings
											
                            
																					
												Downside connection
												Front
											
                            
																					
												Earth-leakage protection
												Without
											
                            
																					
												Mounting support
												Backplate
											
                            
																					
												mechanical durability
												10000 cycles
											
                            
																					
												electrical durability
												2000 cycles at 690 V In
4000 cycles at 690 V In/2
5000 cycles at 440 V In
6000 cycles at 440 V In/2
											
                            
																					
												Network type
												AC
											
                            
																					
												instantaneous protection pick-up adjustment type ii
												Adjustable
											
                            
																					
												Pollution degree
												3 conforming to IEC 60947
											
                            
																					
												short-time protection delay adjustment type tsd
												Adjustable
											
                            
																					
												short-time protection pick-up adjustment type isd
												Adjustable 9 settings
											
                            
																					
												Suitability for isolation
												Yes conforming to EN/IEC 60947-2
											
                            
																					
												Upside connection
												Front
											
                            
																					
												Utilisation category
												Category B
											
                            
																					
												Protection type
												L : for overload protection (long time)
S : for short time short-circuit protection
I : for instantaneous short-circuit protection
G : for ground fault protection
											
                            
																					
												Zone selective interlocking zsi
												Without