Complementary
																					
												control channels
												Programmable loops
											
                            
																					
												Application structure
												1 cyclic/periodic master task
1 periodic fast task
No auxiliary task
64 event tasks
											
                            
																					
												Product certifications
												CE
UL
CSA
RCM
EAC
Merchant Navy
											
                            
																					
												Product or component type
												Processor module
											
                            
																					
												Control parameter
												One CRC on each frame (RTU) Modbus
One LRC on each frame (ASCII) character mode
One LRC on each frame (ASCII) Modbus
											
                            
																					
												Current consumption
												95 mA at 24 V DC
											
                            
																					
												Communication module processor capacity
												2 Ethernet communication module
4 AS-Interface module
											
                            
																					
												Discrete i/o processor capacity
												1024 I/O multi-rack configuration
704 I/O single-rack configuration
											
                            
																					
												bus length
												0…10 m serial link non isolated character mode segment
0…10 m serial link non isolated Modbus segment
0…1000 m serial link isolated character mode segment
0…1000 m serial link isolated Modbus segment
0…15 m character mode point-to-point
0…15 m Modbus point-to-point
											
                            
																					
												marking
												CE
											
                            
																					
												Default size of object areas
												1024 %MWi internal words located internal data
256 %KWi constant words located internal data
512 %Mi located internal bits
											
                            
																					
												Embedded communication service
												Bandwidth management, Ethernet TCP/IP
Data Editor, Ethernet TCP/IP
Modbus TCP messaging, Ethernet TCP/IP
Rack Viewer, Ethernet TCP/IP
SNMP network administrator, Ethernet TCP/IP
											
                            
																					
												Number of slots
												11
											
                            
																					
												number of devices per segment
												0…32 (character mode)
0…32 (Modbus)
											
                            
																					
												Memory description
												Supplied memory card (BMXRMS008MP) backup of programs, constants, symbols and data
Internal RAM 4096 kB
Internal RAM 256 kB data
Internal RAM 3584 kB program constants and symbols
Supplied memory card (BMXRMS008MP) activation of standard web server, class B10
											
                            
																					
												Net weight
												0.205 kg
											
                            
																					
												number of instructions per ms
												6.4 Kinst/ms 65 % Boolean + 35 % fixed arithmetic
8.1 Kinst/ms 100 % Boolean
											
                            
																					
												number of devices
												2 point-to-point character mode
2 point-to-point Modbus
											
                            
																					
												Maximum size of object areas
												256 kB unlocated internal data
32634 %Mi located internal bits
											
                            
																					
												Monitoring
												Diagnostic counters Modbus
Event counters Modbus
											
                            
																					
												Integrated connection type
												Non isolated serial link RJ45 character mode, transmission mode: asynchronous in baseband, RS232C, transmission mode: 2 twisted shielded pairs at 0.3...19.2 kbit/s full duplex
Non isolated serial link RJ45 character mode, transmission mode: asynchronous in baseband, RS485, transmission mode: 1 twisted shielded pair at 0.3...19.2 kbit/s half duplex
Non isolated serial link RJ45, master/slave Modbus, RTU/ASCII, transmission mode: asynchronous in baseband, RS232C, transmission mode: 1 twisted shielded pair at 0.3...19.2 kbit/s half duplex
Non isolated serial link RJ45, master/slave Modbus, RTU/ASCII, transmission mode: asynchronous in baseband, RS485, transmission mode: 1 twisted shielded pair at 0.3...19.2 kbit/s half duplex
USB port at 12 Mbit/s
Ethernet TCP/IP RJ45, transmission mode: 1 twisted pair at 10/100 Mbit/s
											
                            
																					
												Maximum tap links length
												<15 m serial link non isolated character mode segment
 <15 m serial link non isolated Modbus segment
 <40 m serial link isolated character mode segment
 <40 m serial link isolated Modbus segment
											
                            
																					
												Number of racks
												4
											
                            
																					
												execution time per instruction
												0.12 µs Boolean
0.17 µs double-length words
0.25 µs single-length words
1.16 µs floating points
											
                            
																					
												port ethernet
												10BASE-T/100BASE-TX
											
                            
																					
												System overhead
												0.13 ms for fast task
0.7 ms for master task
											
                            
																					
												Requests
												1 K data bytes per request character mode
252 data bytes per RTU request Modbus
504 data bytes per ASCII request Modbus
											
                            
																					
												Status led
												1 LED (green) activity on Ethernet network (ETH ACT)
1 LED (green) processor running (RUN)
1 LED (green) status of Ethernet network (ETH STS)
1 LED (red) data rate (ETH 100)
1 LED (red) I/O module fault (I/O)
1 LED (red) memory card fault (CARD ERR)
1 LED (red) processor or system fault (ERR)
1 LED (yellow) activity on Modbus (SER COM)
											
                            
																					
												number of addresses
												0…248 for character mode
0…248 for Modbus
											
                            
																					
												Supply
												Internal power supply via rack
											
                            
																			 
																	
										Environment
																					
												Directives
												2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
											
                            
																					
												ip degree of protection
												IP20
											
                            
																					
												Range of product
												Modicon M340 automation platform
											
                            
																					
												ambient air temperature for operation
												0…60 °C
											
                            
																					
												Environmental characteristics
												Hazardous location class I division 2
											
                            
																					
												standards
												EN 61131-2
EN/IEC 61010-2-201
UL 61010-2-201
CSA C22.2 No 61010-2-201
IACS E10
EN/IEC 61000-6-5, interface type 1 and type 2
EN/IEC 61850-3, location G
											
                            
																					
												relative humidity
												10…95 % without condensation
											
                            
																					
												protective treatment
												TC