All categories
Compare Cart

BMXMSP0200 - PTO module 2 channels 4 input 24 V DC 4.3 mA 2 connectors 28 pins - Schneider Electric

Expected in 2-4 weeks
BMXMSP0200 - PTO module 2 channels 4 input 24 V DC 4.3 mA 2 connectors 28 pins - Schneider Electric - PTO module 2 channels 4 input 24 V DC 4.3 mA 2 connectors 28 pins - Schneider Electric - 0
BMXMSP0200 - PTO module 2 channels 4 input 24 V DC 4.3 mA 2 connectors 28 pins - Schneider Electric
924,22 €
924,22 € incl. VAT
Text About:
PTO module 2 channels 4 input 24 V DC 4.3 mA 2 connectors 28 pins - Schneider Electric
924,22 €
SPECIFICATIONS
Main
number of channels 2
reverse polarity protection By reverse mounting diode on output
Integrated on input
Complementary
operating threshold > 12 V no error supply voltage
> 8 V error supply voltage
[ures] residual voltage 0.15 V at state 1
Product certifications CE
UL
CSA
RCM
EAC
Merchant Navy
ATEX zone 2/22
IECEx zone 2/22
response time < 200 µs for position completed input and drive ready input
< 60 µs for origin input and proximity input
maximum leakage current 0.05 mA at state 0
Product or component type PTO module
Current consumption 35 mA at 24 V DC preactuator
150 mA at 3.3 V DC typical
200 mA at 3.3 V DC maximum
current state 0 guaranteed <= 1.5 mA
current per channel 0.4 A
current state 1 guaranteed >= 2 mA
Discrete output current 50 mA
input current 4.3 mA
output short-circuit protection By current limiter and electronic circuit breaker
Derating factor Without
output voltage 24 V DC
Discrete input type Current sink yes origin input conforming to IEC 61131-2 type 3
Current sink yes proximity input and limit switch input conforming to IEC 61131-2 type 3
Current sink or source counter in position input conforming to IEC 61131-2 type 3
Current sink or source drive ready, emergency input conforming to IEC 61131-2 type 3
Load impedance ohmic 15000 Ohm
number of outputs 1 pulse output
2 auxiliary output
Local signalling 1 LED (green) for module operating (RUN)
1 LED (red) for external fault (I/O)
1 LED (red) for internal fault, module failure (ERR)
1 LED (green) for download (DL)
8 LEDs (green) for channel status (CH00)
8 LEDs (green) for channel status (CH01)
Insul btwn prim and second 1500 Vrms
Insulation between channels No insulated
voltage state 1 guaranteed >= 11 V
output frequency 200 kHz <0.5 m with USIC and VW3M8210R05
100 kHz <5 m with the normal source input circuit
200 kHz <10 m with the RS422 compatible circuits
Module format Standard
Output overload protection By current limiter and electronic circuit breaker
output voltage limits 19...30 V
voltage state 0 guaranteed 5 V
Number of inputs 4
electrical connection 2 connectors with 28 pins
input voltage 24 V DC
Input compatibility 2-wire/3-wire proximity sensor 19.2…30 V conforming to IEC 947-5-2
Preactuator voltage detection threshold < 8 V error preactuator voltage auxiliary output
< 8 V no error preactuator voltage auxiliary output
> 14 V error preactuator voltage pulse output
> 14 V no error preactuator voltage pulse output
Response time on output 1.2...1.5 ms on appearance
1.2...1.5 ms on disappearance
Output compatibility Signal converter (USIC)
RS422, 7 mA input
Source input, 5 V to 24 V
Environment
Directives 2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
2014/34/EU - ATEX directive
Range of product Modicon X80
ambient air temperature for operation -25…70 °C
Environmental characteristics Hazardous location class I division 2
standards EN/IEC 61131-2
EN/IEC 61010-2-201
UL 61010-2-201
CSA C22.2 No 61010-2-201
IACS E10
EN/IEC 61000-6-5, interface type 1 and type 2
EN/IEC 61850-3, location G
EN/IEC 60079-0
insulation resistance > 10 MOhm
Recently viewed
924,22 €
924,22 € incl. VAT
Expected in 2-4 weeks