Complementary
operating threshold
> 12 V no error supply voltage
> 8 V error supply voltage
[ures] residual voltage
0.15 V at state 1
Product certifications
CE
UL
CSA
RCM
EAC
Merchant Navy
ATEX zone 2/22
IECEx zone 2/22
response time
< 200 µs for position completed input and drive ready input
< 60 µs for origin input and proximity input
maximum leakage current
0.05 mA at state 0
Product or component type
PTO module
Current consumption
35 mA at 24 V DC preactuator
150 mA at 3.3 V DC typical
200 mA at 3.3 V DC maximum
current state 0 guaranteed
<= 1.5 mA
current per channel
0.4 A
current state 1 guaranteed
>= 2 mA
Discrete output current
50 mA
input current
4.3 mA
output short-circuit protection
By current limiter and electronic circuit breaker
Derating factor
Without
output voltage
24 V DC
Discrete input type
Current sink yes origin input conforming to IEC 61131-2 type 3
Current sink yes proximity input and limit switch input conforming to IEC 61131-2 type 3
Current sink or source counter in position input conforming to IEC 61131-2 type 3
Current sink or source drive ready, emergency input conforming to IEC 61131-2 type 3
Load impedance ohmic
15000 Ohm
number of outputs
1 pulse output
2 auxiliary output
Local signalling
1 LED (green) for module operating (RUN)
1 LED (red) for external fault (I/O)
1 LED (red) for internal fault, module failure (ERR)
1 LED (green) for download (DL)
8 LEDs (green) for channel status (CH00)
8 LEDs (green) for channel status (CH01)
Insul btwn prim and second
1500 Vrms
Insulation between channels
No insulated
voltage state 1 guaranteed
>= 11 V
output frequency
200 kHz <0.5 m with USIC and VW3M8210R05
100 kHz <5 m with the normal source input circuit
200 kHz <10 m with the RS422 compatible circuits
Module format
Standard
Output overload protection
By current limiter and electronic circuit breaker
output voltage limits
19...30 V
voltage state 0 guaranteed
5 V
Number of inputs
4
electrical connection
2 connectors with 28 pins
input voltage
24 V DC
Input compatibility
2-wire/3-wire proximity sensor 19.2…30 V conforming to IEC 947-5-2
Preactuator voltage detection threshold
< 8 V error preactuator voltage auxiliary output
< 8 V no error preactuator voltage auxiliary output
> 14 V error preactuator voltage pulse output
> 14 V no error preactuator voltage pulse output
Response time on output
1.2...1.5 ms on appearance
1.2...1.5 ms on disappearance
Output compatibility
Signal converter (USIC)
RS422, 7 mA input
Source input, 5 V to 24 V
Environment
Directives
2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
2014/34/EU - ATEX directive
Range of product
Modicon X80
ambient air temperature for operation
-25…70 °C
Environmental characteristics
Hazardous location class I division 2
standards
EN/IEC 61131-2
EN/IEC 61010-2-201
UL 61010-2-201
CSA C22.2 No 61010-2-201
IACS E10
EN/IEC 61000-6-5, interface type 1 and type 2
EN/IEC 61850-3, location G
EN/IEC 60079-0
insulation resistance
> 10 MOhm