Main
Discrete output logic
Positive or negative configurable
product specific application
For severe environments
number of channels
2
Complementary
maximum output current
2 A per module
0.5 A per output
Product certifications
CE
UL
CSA
RCM
EAC
Merchant Navy
maximum leakage current
0.1 mA at state 0
Product or component type
Counter module
Current consumption
200 mA at 3.3 V DC bus
40 mA at 24 V DC rack
80 mA at 24 V DC sensor
maximum voltage drop
<3 V at state 1
current state 0 guaranteed
<= 1.5 mA
current state 1 guaranteed
>= 6 mA
input current
2 mA at 11 V
output short-circuit protection
1.5 A integrated
output voltage
24 V DC
Counter function
Ratio count
Frequency meter
Down counting
32-bit counter counting
Loop (modulo) counting
Measure time periods
Count events
Width modulation
input voltage limits
19.2...30 V at 60 °C
26.4 V at 70 °C
number of outputs
2
input type
3 auxiliary input
3 high speed
overlap time
0.2 ms
Net weight
0.112 kg
voltage state 1 guaranteed
11...30 V
Module format
Standard
Output overload protection
Integrated
output voltage limits
19.2...30 V
voltage state 0 guaranteed
< 5 V
Number of inputs
6
electrical connection
1 connector with 10 pins for wiring auxiliary input and sensor power supply
1 connector with 16 pins for wiring the sensors of counter 0
1 connector with 16 pins for wiring the sensors of counter 1
input voltage
24 V DC type 3
Maximum counting frequency
60000 Hz
Isolation voltage
1500 V for 60 s
Maximum load current
1 A per module
0.5 A per output
Input compatibility
19.2…30 V 2-wire/3-wire proximity sensor
incremental encoder with push-pull outputs, 10...30 V totem pole
cycle time
1 ms
Environment
Directives
2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
ip degree of protection
IP20
Range of product
Modicon M340 automation platform
ambient air temperature for operation
-25…70 °C
Environmental characteristics
Gas resistant class Gx conforming to ISA S71.04
Gas resistant class 3C4 conforming to IEC 60721-3-3
Dust resistant class 3S4 conforming to IEC 60721-3-3
Sand resistant class 3S4 conforming to IEC 60721-3-3
Salt resistant level 2 conforming to IEC 68252
Mold growth resistant class 3B2 conforming to IEC 60721-3-3
Fungal spore resistant class 3B2 conforming to IEC 60721-3-3
Hazardous location class I division 2
standards
EN 61131-2
EN/IEC 61010-2-201
UL 61010-2-201
CSA C22.2 No 61010-2-201
IACS E10
EN/IEC 61000-6-5, interface type 1 and type 2
EN/IEC 61850-3, location G
relative humidity
10…95 % without condensation
protective treatment
Conformal coating