SPECIFICATIONS
Main
product specific application For severe environments
Complementary
[ith] conventional thermal current 2 A
mtbf reliability 2100000 H
Product or component type Discrete output module
minimum switching current 1 mA 5 V DC
output short-circuit protection Use 1 fast blow fuse per channel or group of channel
Net weight 0.15 kg
Discrete output type Relay
Discrete output voltage 24...48 V 19...60 V DC
24...240 V 19…264 V AC
Discrete output number 16 conforming to EN/IEC 61131-2
power dissipation in w 3 W
electrical durability AC-15: 100000 cycles at 240 VA 200 V (load factor 0.7)
AC-15: 100000 cycles at 120 VA 200 V (load factor 0.35)
AC-12: 100000 cycles at 200 VA 100 V
AC-12: 100000 cycles at 80 VA 48 V
AC-12: 100000 cycles at 50 VA 24 V
AC-15: 100000 cycles at 120 VA 100 V
AC-15: 100000 cycles at 120 VA 24 V
AC-15: 100000 cycles at 120 VA 48 V
DC-12: 100000 cycles at 24 W 24 V
DC-13: 100000 cycles at 10 W 24 V
DC-13: 100000 cycles at 10 W 48 V
AC-15: 300000 cycles at 72 VA 200 V (load factor 0.7)
AC-15: 300000 cycles at 36 VA 200 V (load factor 0.35)
AC-12: 300000 cycles at 200 VA 200 V
AC-12: 300000 cycles at 80 VA 100 V
AC-12: 300000 cycles at 50 VA 48 V
AC-15: 300000 cycles at 36 VA 100 V
AC-15: 300000 cycles at 72 VA 100 V
AC-15: 300000 cycles at 36 VA 48 V
AC-15: 300000 cycles at 72 VA 48 V
AC-15: 300000 cycles at 36 VA 24 V
AC-15: 300000 cycles at 72 VA 24 V
DC-13: 300000 cycles at 3 W 24 V
DC-13: 300000 cycles at 3 W 48 V
DC-13: 7000 cycles at 24 W 24 V
DC-13: 7000 cycles at 24 W 48 V
DC-12: 50000 cycles at 24 W 48 V
Output overload protection Use 1 fast blow fuse per channel or group of channel
dielectric strength 2000 V AC at 50/60 Hz 1 min
Output overvoltage protection Use discharge diode on each output DC
Use RC circuit on each output AC
Use ZNO surge limiter on each output AC
Shock resistance 30 gn
Response time on output < 8 ms activation
< 10 ms deactivation
Status led 1 LED (green) RUN
1 LED per channel (green) channel diagnostic
1 LED (red) ERR
1 LED (red) I/O
Typical current consumption 79 mA at 3.3 V DC
Environment
Ambient air temp for storage/transportation -40…85 °C
Directives 2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
ip degree of protection IP20
operating altitude 0...2000 m
2000...5000 m with derating factor
Range of product Modicon X80
ambient air temperature for operation -25…70 °C
Environmental characteristics Gas resistant class Gx
Gas resistant class 3C4
Dust resistant class 3S4
Sand resistant class 3S4
Salt resistant level 2
Mold growth resistant class 3B2
Fungal spore resistant class 3B2
relative humidity 5…95 % at 55 °C without condensation
vibration resistance 3 gn
protective treatment Conformal coating
insulation resistance > 10 MOhm 500 V DC