Main
Discrete output logic
Positive
product specific application
For severe environments
Complementary
[ith] conventional thermal current
3 A
mtbf reliability
3200000 H
Product or component type
Relay discrete output module
minimum switching current
1 mA 5 V DC
network frequency limits
47…63 Hz
output short-circuit protection
Use 1 fast blow fuse per channel or group of channel
network frequency
50/60 Hz
Net weight
0.169 kg
Discrete output voltage
24...240 V 19...264 V AC
24...125 V 5...150 V DC
Discrete output number
8 conforming to EN/IEC 61131-2
power dissipation in w
3.6 W
electrical durability
AC-12: 200000 cycles at 48 VA 24 V at -25…60 °C
AC-12: 200000 cycles at 28.8 VA 24 V at 70 °C
AC-12: 300000 cycles at 48 VA 48 V at -25…60 °C
AC-12: 300000 cycles at 28.8 VA 48 V at 70 °C
AC-12: 150000 cycles at 96 VA 48 V at -25…60 °C
AC-12: 150000 cycles at 57.6 VA 48 V at 70 °C
AC-12: 300000 cycles at 110 VA 100...120 V at -25…60 °C
AC-12: 300000 cycles at 66 VA 100...120 V at 70 °C
AC-12: 150000 cycles at 220 VA 100...120 V at -25…60 °C
AC-12: 150000 cycles at 132 VA 100...120 V at 70 °C
AC-12: 300000 cycles at 220 VA 200...250 V at -25…60 °C
AC-12: 300000 cycles at 132 VA 200...250 V at 70 °C
AC-12: 150000 cycles at 500 VA 200...250 V at -25…60 °C
AC-12: 150000 cycles at 300 VA 200...250 V at 70 °C
AC-15: 700000 cycles at 10 VA 24 V at -25…60 °C (load factor 0.4)
AC-15: 700000 cycles at 6 VA 24 V at 70 °C (load factor 0.4)
AC-15: 500000 cycles at 24 VA 24 V at -25…60 °C (load factor 0.4)
AC-15: 500000 cycles at 14.4 VA 24 V at 70 °C (load factor 0.4)
AC-15: 200000 cycles at 48 VA 24 V at -25…60 °C (load factor 0.4)
AC-15: 200000 cycles at 28.8 VA 24 V at 70 °C (load factor 0.4)
AC-15: 700000 cycles at 10 VA 48 V at -25…60 °C (load factor 0.4)
AC-15: 700000 cycles at 6 VA 48 V at 70 °C (load factor 0.4)
AC-15: 500000 cycles at 24 VA 48 V at -25…60 °C (load factor 0.4)
AC-15: 500000 cycles at 14.4 VA 48 V at 70 °C (load factor 0.4)
AC-15: 300000 cycles at 48 VA 48 V at -25…60 °C (load factor 0.4)
AC-15: 300000 cycles at 28.8 VA 48 V at 70 °C (load factor 0.4)
AC-15: 100000 cycles at 96 VA 48 V at -25…60 °C (load factor 0.4)
AC-15: 100000 cycles at 57.6 VA 48 V at 70 °C (load factor 0.4)
AC-15: 1000000 cycles at 10 VA 100...120 V at -25…60 °C (load factor 0.4)
AC-15: 1000000 cycles at 6 VA 100...120 V at 70 °C (load factor 0.4)
AC-15: 300000 cycles at 50 VA 100...120 V at -25…60 °C (load factor 0.4)
AC-15: 300000 cycles at 30 VA 100...120 V at 70 °C (load factor 0.4)
AC-15: 200000 cycles at 110 VA 100...120 V at -25…60 °C (load factor 0.4)
AC-15: 200000 cycles at 66 VA 100...120 V at 70 °C (load factor 0.4)
AC-15: 70000 cycles at 220 VA 100...120 V at -25…60 °C (load factor 0.4)
AC-15: 70000 cycles at 132 VA 100...120 V at 70 °C (load factor 0.4)
AC-15: 1000000 cycles at 10 VA 200...250 V at -25…60 °C (load factor 0.4)
AC-15: 1000000 cycles at 6 VA 200...250 V at 70 °C (load factor 0.4)
AC-15: 500000 cycles at 50 VA 200...250 V at -25…60 °C (load factor 0.4)
AC-15: 500000 cycles at 30 VA 200...250 V at 70 °C (load factor 0.4)
AC-15: 200000 cycles at 110 VA 200...250 V at -25…60 °C (load factor 0.4)
AC-15: 200000 cycles at 66 VA 200...250 V at 70 °C (load factor 0.4)
AC-15: 150000 cycles at 220 VA 200...250 V at -25…60 °C (load factor 0.4)
AC-15: 150000 cycles at 132 VA 200...250 V at 70 °C (load factor 0.4)
DC-12: 200000 cycles at 24 W 24 V at -25…60 °C
DC-12: 200000 cycles at 14.4 W 24 V at 70 °C
DC-12: 150000 cycles at 48 W 24 V at -25…60 °C
DC-12: 150000 cycles at 28.8 W 24 V at 70 °C
DC-12: 150000 cycles at 40 W 48...60 V at -25…60 °C
DC-12: 150000 cycles at 24 W 48...60 V at 70 °C
DC-12: 100000 cycles at 45 W 100...125 V at -25…60 °C
DC-12: 60000 cycles at 45 W 100...125 V at 70 °C
DC-13: 100000 cycles at 10 W 24 V at -25…60 °C
DC-13: 100000 cycles at 6 W 24 V at 70 °C
DC-13: 60000 cycles at 24 W 24 V at -25…60 °C
DC-13: 60000 cycles at 14.4 W 24 V at 70 °C
DC-13: 40000 cycles at 48 W 24 V at -25…60 °C
DC-13: 40000 cycles at 28.8 W 24 V at 70 °C
DC-13: 40000 cycles at 40 W 48...60 V at -25…60 °C
DC-13: 40000 cycles at 24 W 48...60 V at 70 °C
DC-13: 100000 cycles at 15 W 100...125 V at -25…60 °C
DC-13: 40000 cycles at 15 W 100...125 V at 70 °C
Output overload protection
Use 1 fast blow fuse per channel or group of channel
electrical connection
20 ways terminal block
dielectric strength
1780 V AC at 50/60 Hz 1 min
Sensor power supply
5...150 V
19...264 V
Output overvoltage protection
Use discharge diode on each output DC
Use RC circuit on each output AC
Use ZNO surge limiter on each output AC
Shock resistance
30 gn
Response time on output
<= 10 ms activation
<= 13 ms deactivation
Status led
1 LED (green) RUN
1 LED per channel (green) channel diagnostic
1 LED (red) ERR
1 LED (red) I/O
Protection type
External short-circuit protection
External overload protection
External overvoltage protection, inductive AC network
External overvoltage protection, inductive DC network
Typical current consumption
40 mA at 3.3 V DC
101 mA at 24 V DC
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP20
operating altitude
0...2000 m
2000...5000 m with derating factor
Range of product
Modicon X80
ambient air temperature for operation
-25…70 °C
Environmental characteristics
Gas resistant class Gx
Gas resistant class 3C4
Dust resistant class 3S4
Sand resistant class 3S4
Salt resistant level 2
Mold growth resistant class 3B2
Fungal spore resistant class 3B2
relative humidity
0…95 % at 60 °C without condensation
vibration resistance
3 gn
protective treatment
Conformal coating
insulation resistance
> 10 MOhm 500 V DC