Main
Discrete input current
3.5 mA
product specific application
For severe environments
Complementary
mtbf reliability
940000 H
Product or component type
Discrete I/O module
Dc maximum response time
7 ms
current state 0 guaranteed
<= 1.5 mA
Dc typical response time
4 ms
minimum switching current
1 mA 5 V DC
paralleling of inputs
No
current state 1 guaranteed
>= 2 mA
Discrete output current
2000 mA
switching frequency
1 Hz
Discrete input voltage
24 V DC, discrete input logic: positive
input type
Current sink (logic positive)
Discrete input number
8
Net weight
0.135 kg
Discrete output type
Relay
Discrete output voltage
24 V 19...30 V DC
24...240 V 19...264 V AC
Discrete output number
8
input impedance
6800 Ohm
mechanical durability
20000000 cycles
power dissipation in w
3.1 W
electrical durability
AC-14: 100000 cycles at 120 VA 240 V at 70 °C (load factor 0.7)
AC-14: 100000 cycles at 150 VA 200 V at 70 °C (load factor 0.7)
AC-14: 100000 cycles at 240 VA 240 V at -25…60 °C (load factor 0.7)
AC-14: 100000 cycles at 300 VA 200 V at -25…60 °C (load factor 0.7)
AC-15: 100000 cycles at 100 VA 200 V at 70 °C (load factor 0.35)
AC-15: 100000 cycles at 120 VA 240 V at -25…60 °C (load factor 0.35)
AC-15: 100000 cycles at 200 VA 200 V at -25…60 °C (load factor 0.35)
AC-15: 100000 cycles at 60 VA 240 V at 70 °C (load factor 0.35)
DC-13: 100000 cycles at 12 W 24 V at 70 °C
DC-13: 100000 cycles at 24 W 24 V at -25…60 °C
AC-14: 300000 cycles at 36 VA 240 V at 70 °C (load factor 0.7)
AC-14: 300000 cycles at 40 VA 200 V at 70 °C (load factor 0.7)
AC-14: 300000 cycles at 72 VA 240 V at -25…60 °C (load factor 0.7)
AC-14: 300000 cycles at 80 VA 200 V at -25…60 °C (load factor 0.7)
AC-15: 300000 cycles at 18 VA 240 V at 70 °C (load factor 0.35)
AC-15: 300000 cycles at 30 VA 200 V at 70 °C (load factor 0.35)
AC-15: 300000 cycles at 36 VA 240 V at -25…60 °C (load factor 0.35)
AC-15: 300000 cycles at 60 VA 200 V at -25…60 °C (load factor 0.35)
DC-13: 300000 cycles at 3.6 W 24 V at 70 °C
DC-13: 300000 cycles at 7.2 W 24 V at -25…60 °C
Maximum switching voltage
125 V DC
264 V AC
voltage detection threshold
< 14 V DC sensor fault
> 18 V DC sensor OK
dielectric strength
1500 V AC at 50/60 Hz 1 minute, primary/secondary
2830 V AC at 50/60 Hz 1 minute, output relay
500 V DC 1 minute, between group of I/O
Sensor power supply
19...30 V 60 °C
21.1...29.0 V 70 °C
Input compatibility
With 2-wire/3-wire proximity sensors conforming to IEC 60947-5-2
With 2-wire/3-wire proximity sensors conforming to IEC 61131-2 type 3
Shock resistance
30 gn
Response time on output
<= 8 ms deactivation
<= 10 ms activation
Status led
1 LED (green) module operating (RUN)
1 LED per channel (green) channel diagnostic
1 LED (red) module error (ERR)
1 LED (red) module I/O
Protection type
1 external fuse per group of input channel0.5 A fast blow
reverse polarity protection on input
1 external fuse per output channel or group of output channel fast blow
Typical current consumption
79 mA at 3.3 V DC
Environment
Ambient air temp for storage/transportation
-40…85 °C
Directives
2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
ip degree of protection
IP20
operating altitude
0...2000 m
2000...5000 m with derating factor
Range of product
Modicon X80
ambient air temperature for operation
-25…70 °C
Environmental characteristics
Gas resistant class Gx
Gas resistant class 3C4
Dust resistant class 3S4
Sand resistant class 3S4
Salt resistant level 2
Mold growth resistant class 3B2
Fungal spore resistant class 3B2
relative humidity
5…95 % at 55 °C without condensation
vibration resistance
3 gn
protective treatment
Conformal coating
insulation resistance
> 10 MOhm 500 V DC