Main
product specific application
For severe environments
Complementary
maximum leakage current
1 mA at state 0 24 V
1 mA at state 0 48 V
2 mA at state 0 115 V
2.5 mA at state 0 240 V
mtbf reliability
500000 H
Product or component type
Discrete output module
inrush current
30 A
maximum voltage drop
<1.55 V at state 1
current per channel
1.2 A at 60 °C
0.6 A at 70 °C
network frequency limits
47…63 Hz
Discrete output current
1.2 A
Maximum current per output common
4 A
network frequency
50/60 Hz
Maximum current per module
4 A 60 °C
2 A 70 °C
Net weight
0.264 kg
Discrete output type
Triac
Discrete output voltage
24...240 V 20...264 V AC
Output current limits
0.005…10 A
Discrete output number
16 conforming to EN/IEC 61131-2
power dissipation in w
1.45 W
Output overload protection
With varistor
dielectric strength
3000 V AC at 50/60 Hz 1 min
Sensor power supply
20...264 V
Shock resistance
30 gn
Response time on output
<= 10 ms resistive activation
<= 10 ms resistive deactivation
Status led
1 LED (green) module operating (RUN)
1 LED per channel (green) channel diagnostic
1 LED (red) module error (ERR)
1 LED (red) module I/O
Protection type
1 external fuse4 A fast blow
Typical current consumption
61 mA at 3.3 V DC
50 mA at 24 V DC
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP20
operating altitude
0...2000 m
2000...5000 m with derating factor
Range of product
Modicon X80
ambient air temperature for operation
-25…70 °C
Environmental characteristics
Gas resistant class Gx
Gas resistant class 3C4
Dust resistant class 3S4
Sand resistant class 3S4
Salt resistant level 2
Mold growth resistant class 3B2
relative humidity
0…95 % at -25…70 °C without condensation
vibration resistance
3 gn
protective treatment
Conformal coating
insulation resistance
> 10 MOhm 500 V DC