Main
Advanced diagnostics available via network
Redundancy information
Redundancy test
Temperature sensing
Remaining lifetime
Uptime duration
Backplane compatibility
All backplane
Primary voltage
24...48 V
Secondary power
18 W 3.3 V DC at 0…60 °C I/O module logic power supply
40 W 24 V DC at 0…60 °C I/O module power supply and processor if 3.3 V not loaded
i²t at switch-on
0.4 A².s 24 V
1.9 A².s 48 V
Complementary
Control type
RESET push-button cold restart
Current at secondary voltage
5.5 A 3.3 V DC I/O module logic power supply
1.67 A 24 V DC I/O module power supply and processor
mtbf reliability
752000 H
Product or component type
Power supply module
inrush current
60 A 48 V
60 A 24 V
maximum power dissipation in w
8.5 W
input current
1.9 A 24 V
1 A 48 V
It on activation
0.05 A.s 24 V
0.08 A.s 48 V
Net weight
0.81 kg
Maximum cable distance between devices
10 m
15 m
Immunity to microbreaks
1 ms
Primary voltage limit
18...62.4 V
electrical connection
1 connector 2 pin(s)alarm relay
1 connector 5 pin(s)line supply, protective earth
dielectric strength
1500 V primary/ground
1500 V primary/secondary
Status led
1 LED (green) presence of voltages (OK)
1 LED (green) redundancy OK
1 LED (green) power supply status
Supply circuit type
DC
Protection type
Internal fuse not accessible for primary circuit
Overload protection for secondary circuit
Overvoltage protection for secondary circuit
Short-circuit protection for secondary circuit
Environment
Ambient air temp for storage/transportation
-40…85 °C
Directives
2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
ip degree of protection
IP20
Range of product
Modicon X80
ambient air temperature for operation
0…60 °C
Environmental characteristics
3C3 conforming to EN/IEC 60721-3-3
3C4 conforming to EN/IEC 60721-3-3
relative humidity
10…95 % without condensation
insulation resistance
>= 100 MOhm primary/ground
>= 100 MOhm primary/secondary