Main
Advanced diagnostics available via network
Remaining lifetime
Temperature sensing
Redundancy test
Redundancy information
Uptime duration
Backplane compatibility
All backplane
Primary voltage
100...240 V
product specific application
For severe environments
Secondary power
18 W 3.3 V DC at -25…70 °C I/O module logic power supply
40 W 24 V DC at -25…70 °C I/O module power supply and processor if 3.3 V not loaded
i²t at switch-on
1 A².s 120 V
3 A².s 240 V
Complementary
Control type
RESET push-button cold restart
Product certifications
CE
UL
CSA
RCM
EAC
Merchant Navy
Current at secondary voltage
5.5 A 3.3 V DC I/O module logic power supply
1.67 A 24 V DC I/O module power supply and processor
mtbf reliability
792000 H
Product or component type
Power supply module
inrush current
30 A 120 V
60 A 240 V
network frequency limits
47…63 Hz
maximum power dissipation in w
8.5 W
input current
0.52 A 240 V
1.04 A 115 V
network frequency
50/60 Hz
It on activation
0.05 A.s 120 V
0.07 A.s 240 V
Net weight
0.51 kg
Immunity to microbreaks
1 ms
Primary voltage limit
85...264 V
electrical connection
1 connector 2 pin(s)alarm relay
1 connector 5 pin(s)line supply, protective earth
dielectric strength
1500 V primary/secondary I/O module logic power supply
1500 V primary/secondary I/O module power supply and processor
2300 V primary/secondary sensor power supply
1500 V primary/ground
500 V 24 V sensor output/ground
Shock resistance
30 gn
Status led
1 LED (green) presence of voltages (OK)
1 LED (green) redundancy OK
1 LED (green) power supply status
apparent power
0.13 kVA
Supply circuit type
AC
Protection type
Internal fuse not accessible for primary circuit
Overload protection for secondary circuit
Overvoltage protection for secondary circuit
Short-circuit protection for secondary circuit
Environment
Ambient air temp for storage/transportation
-40…85 °C
Directives
2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
ip degree of protection
IP20
operating altitude
0...2000 m
2000...5000 m with derating factor
Range of product
Modicon X80
ambient air temperature for operation
-25…70 °C
Environmental characteristics
Gas resistant class Gx conforming to ISA S71.04
Gas resistant class 3C4 conforming to IEC 60721-3-3
Dust resistant class 3S4 conforming to IEC 60721-3-3
Sand resistant class 3S4 conforming to IEC 60721-3-3
Salt resistant level 2 conforming to IEC 68252
Mold growth resistant class 3B2 conforming to IEC 60721-3-3
Fungal spore resistant class 3B2 conforming to IEC 60721-3-3
Hazardous location class I division 2
standards
EN 61131-2
EN/IEC 61010-2-201
UL 61010-2-201
CSA C22.2 No 61010-2-201
IACS E10
EN/IEC 61000-6-5, interface type 1 and type 2
EN/IEC 61850-3, location G
relative humidity
5…95 % at 55 °C without condensation
vibration resistance
3 gn
protective treatment
Conformal coating
insulation resistance
>= 100 MOhm primary/ground
>= 100 MOhm primary/secondary