SPECIFICATIONS
Main
Backplane compatibility Not compatible with BMEXBP..02
Primary voltage 100...240 V
product specific application For severe environments
Secondary power 15 W 3.3 V DC at 0…60 °C I/O module logic power supply
31.2 W 24 V DC at 0…60 °C I/O module power supply and processor
11.3 W 3.3 V DC at -25…70 °C I/O module logic power supply
23.4 W 24 V DC at -25…70 °C I/O module power supply and processor
21.6 W 24 V DC at 0…60 °C sensor power supply
16.2 W 24 V DC at -25…70 °C sensor power supply
i²t at switch-on 1 A².s 120 V
3 A².s 240 V
Complementary
Control type RESET push-button cold restart
Product certifications CE
UL
CSA
RCM
EAC
Merchant Navy
Current at secondary voltage 0.9 A 24 V DC sensor power supply
1.3 A 24 V DC I/O module power supply and processor
4.5 A 3.3 V DC I/O module logic power supply
mtbf reliability 4300000 H
Product or component type Power supply module
inrush current 30 A 120 V
60 A 240 V
network frequency limits 47…63 Hz
maximum power dissipation in w 8.5 W
input current 0.52 A 240 V
1.04 A 115 V
network frequency 50/60 Hz
It on activation 0.05 A.s 120 V
0.07 A.s 240 V
Net weight 0.36 kg
Immunity to microbreaks 1 ms
Primary voltage limit 85...264 V
electrical connection 1 connector 2 pin(s)alarm relay
1 connector 5 pin(s)line supply, protective earth, 24 V DC input sensor
dielectric strength 1500 V primary/secondary I/O module logic power supply
1500 V primary/secondary I/O module power supply and processor
2300 V primary/secondary sensor power supply
1500 V primary/ground
500 V 24 V sensor output/ground
Shock resistance 30 gn
Status led 1 LED (green) rack voltage OK
1 LED (green) sensor voltage
apparent power 0.12 kVA
Supply circuit type AC
Protection type Internal fuse not accessible for primary circuit
Overload protection for secondary circuit
Overvoltage protection for secondary circuit
Short-circuit protection for secondary circuit
Environment
Ambient air temp for storage/transportation -40…85 °C
Directives 2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
ip degree of protection IP20
operating altitude 0...2000 m
2000...5000 m with derating factor
Range of product Modicon X80
ambient air temperature for operation -25…70 °C
Environmental characteristics Gas resistant class Gx conforming to ISA S71.04
Gas resistant class 3C4 conforming to IEC 60721-3-3
Dust resistant class 3S4 conforming to IEC 60721-3-3
Sand resistant class 3S4 conforming to IEC 60721-3-3
Salt resistant level 2 conforming to IEC 68252
Mold growth resistant class 3B2 conforming to IEC 60721-3-3
Fungal spore resistant class 3B2 conforming to IEC 60721-3-3
Hazardous location class I division 2
standards EN 61131-2
EN/IEC 61010-2-201
UL 61010-2-201
CSA C22.2 No 61010-2-201
IACS E10
EN/IEC 61000-6-5, interface type 1 and type 2
EN/IEC 61850-3, location G
relative humidity 5…95 % at 55 °C without condensation
vibration resistance 3 gn
protective treatment Conformal coating
insulation resistance >= 100 MOhm primary/ground
>= 100 MOhm primary/secondary