Main
Backplane compatibility
Not compatible with BMEXBP..02
Primary voltage
24...48 V isolated
Secondary power
15 W 3.3 V DC I/O module logic power supply
31.2 W 24 V DC I/O module power supply and processor
i²t at switch-on
1 A².s 24 V
3 A².s 48 V
Complementary
Control type
RESET push-button cold restart
Current at secondary voltage
1.3 A 24 V DC I/O module power supply and processor
4.5 A 3.3 V DC I/O module logic power supply
mtbf reliability
4600000 H
Product or component type
Power supply module
inrush current
30 A 24 V
60 A 48 V
maximum power dissipation in w
8.5 W
input current
0.83 A 48 V
1.65 A 24 V
It on activation
0.2 A.s 24 V
0.3 A.s 48 V
Net weight
0.34 kg
Maximum cable distance between devices
10 m power supply cable copper 1.5 mm²
15 m power supply cable copper 2.5 mm²
Immunity to microbreaks
1 ms
Primary voltage limit
18...62.4 V
electrical connection
1 connector 2 pin(s)alarm relay
1 connector 5 pin(s)line supply, protective earth
dielectric strength
1500 V primary/ground
1500 V primary/secondary
Shock resistance
30 gn
Status led
1 LED (green) rack voltage OK
Supply circuit type
DC
Protection type
Internal fuse not accessible for primary circuit
Overload protection for secondary circuit, 24 V sensor power supply
Overvoltage protection for secondary circuit, 24 V sensor power supply
Short-circuit protection for secondary circuit, 24 V sensor power supply
Environment
Ambient air temp for storage/transportation
-40…85 °C
Directives
2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
ip degree of protection
IP20
operating altitude
0...2000 m
2000...5000 m with derating factor
Range of product
Modicon X80
ambient air temperature for operation
0…60 °C
relative humidity
5…95 % at 55 °C without condensation
vibration resistance
3 gn
protective treatment
TC
insulation resistance
>= 10 MOhm primary/ground
>= 10 MOhm primary/secondary