SPECIFICATIONS
Main
Backplane compatibility Not compatible with BMEXBP..02
Primary voltage 100...240 V
Secondary power 10.8 W 24 V DC sensor power supply
16.8 W 24 V DC I/O module power supply and processor
8.3 W 3.3 V DC I/O module logic power supply
i²t at switch-on 12 A².s 240 V
Complementary
Control type RESET push-button cold restart
Current at secondary voltage 0.45 A 24 V DC sensor power supply
0.7 A 24 V DC I/O module power supply and processor
2.5 A 3.3 V DC I/O module logic power supply
mtbf reliability 4638000 H
Product or component type Power supply module
inrush current 30 A 120 V
60 A 240 V
network frequency limits 47…63 Hz
maximum power dissipation in w 8.5 W
input current 0.31 A 240 V
0.61 A 115 V
network frequency 50/60 Hz
It on activation 0.06 A.s 240 V
0.03 A.s 120 V
Net weight 0.3 kg
Immunity to microbreaks 1 ms
Primary voltage limit 85...264 V
electrical connection 1 connector 2 pin(s)alarm relay
1 connector 5 pin(s)line supply, protective earth, 24 V DC input sensor
dielectric strength 1500 V primary/secondary I/O module logic power supply
1500 V primary/secondary I/O module power supply and processor
2300 V primary/secondary sensor power supply
1500 V primary/ground
500 V 24 V sensor output/ground
Shock resistance 30 gn
Status led 1 LED (green) rack voltage OK
1 LED (green) sensor voltage
apparent power 0.07 kVA
Supply circuit type AC
Protection type Internal fuse not accessible for primary circuit
Overload protection for secondary circuit
Overvoltage protection for secondary circuit
Short-circuit protection for secondary circuit
Environment
Ambient air temp for storage/transportation -40…85 °C
Directives 2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
ip degree of protection IP20
operating altitude 0...2000 m
2000...5000 m with derating factor
Range of product Modicon X80
ambient air temperature for operation 0…60 °C
relative humidity 5…95 % at 55 °C without condensation
vibration resistance 3 gn
protective treatment TC
insulation resistance >= 100 MOhm primary/ground
>= 100 MOhm primary/secondary