All categories
Compare Cart

BMXART0414 - Analog isolated low level input module, Modicon X80, 4 inputs, 40mV positive or negative - Schneider Electric

Expected in 2-4 weeks
BMXART0414 - Analog isolated low level input module, Modicon X80, 4 inputs, 40mV positive or negative - Schneider Electric - Analog isolated low level input module, Modicon X80, 4 inputs, 40mV positive or negative - Schneider Electric - 0
BMXART0414 - Analog isolated low level input module, Modicon X80, 4 inputs, 40mV positive or negative - Schneider Electric
454,72 €
454,72 € incl. VAT
Text About:
Analog isolated low level input module, Modicon X80, 4 inputs, 40mV positive or negative - Schneider Electric
454,72 €
SPECIFICATIONS
Main
Analogue input resolution 15 bits + sign
Input level Low level
type of filter First order digital filtering
Complementary
Analog/digital conversion Sigma delta 16 bits
Product certifications EAC
RCM
UL
Merchant Navy
CSA
CE
mtbf reliability 1400000 H
Product or component type Analog input module
Current consumption 150 mA at 3.3 V DC
40 mA at 24 V DC
Cold junction compensation External by Pt100 probe
Analogue input number 4
Common mode rejection 120 dB 50/60 Hz
Detection type Open circuit Cu 10
Open circuit Ni 100
Open circuit Ni 1000
Open circuit Pt 100
Open circuit Pt 1000
Open circuit thermocouple B
Open circuit thermocouple E
Open circuit thermocouple J
Open circuit thermocouple K
Open circuit thermocouple L
Open circuit thermocouple N
Open circuit thermocouple R
Open circuit thermocouple S
Open circuit thermocouple T
Open circuit thermocouple U
Analogue input type Voltage +/- 1.28 V
Voltage +/- 160 mV
Voltage +/- 320 mV
Voltage +/- 40 mV
Voltage +/- 640 mV
Voltage +/- 80 mV
Resistor 400 Ohm 2 wires
Resistor 400 Ohm 3 wires
Resistor 400 Ohm 4 wires
Resistor 4000 Ohm 2 wires
Resistor 4000 Ohm 3 wires
Resistor 4000 Ohm 4 wires
Temperature probe -100...+260 °C Cu 10
Temperature probe -100...+450 °C Pt 100 conforming to UL/JIS
Temperature probe -100...+450 °C Pt 1000 conforming to UL/JIS
Temperature probe -200...+850 °C Pt 100 conforming to IEC
Temperature probe -200...+850 °C Pt 1000 conforming to IEC
Temperature probe -60...+180 °C Ni 100
Temperature probe -60...+180 °C Ni 1000
Thermocouple +130...+1820 °C thermocouple B
Thermocouple +270...+1300 °C thermocouple N
Thermocouple -200...+600 °C thermocouple U
Thermocouple -200...+760 °C thermocouple J
Thermocouple -200...+900 °C thermocouple L
Thermocouple -270...+1000 °C thermocouple E
Thermocouple -270...+1370 °C thermocouple K
Thermocouple -270...+400 °C thermocouple T
Thermocouple -50...+1769 °C thermocouple R
Thermocouple -50...+1769 °C thermocouple S
Differential mode rejection 60 dB 50/60 Hz
temperature drift 25 ppm/°C 400 Ohm
25 ppm/°C 4000 Ohm
25 ppm/°C Ni 1000
25 ppm/°C thermocouple B
25 ppm/°C thermocouple E
25 ppm/°C thermocouple J
25 ppm/°C thermocouple K
25 ppm/°C thermocouple L
25 ppm/°C thermocouple N
25 ppm/°C thermocouple R
25 ppm/°C thermocouple S
25 ppm/°C thermocouple T
25 ppm/°C thermocouple U
30 ppm/°C +/- 1.28 V
30 ppm/°C +/- 160 mV
30 ppm/°C +/- 320 mV
30 ppm/°C +/- 40 mV
30 ppm/°C +/- 640 mV
30 ppm/°C +/- 80 mV
30 ppm/°C Cu 10
30 ppm/°C Ni 100
30 ppm/°C Pt 100
30 ppm/°C Pt 1000
Net weight 0.135 kg
Maximum conversion value +/- 100 % 400 Ohm
+/- 100 % 4000 Ohm
+/- 102.5 % +/- 1.28 V
+/- 102.5 % +/- 160 mV
+/- 102.5 % +/- 320 mV
+/- 102.5 % +/- 40 mV
+/- 102.5 % +/- 640 mV
+/- 102.5 % +/- 80 mV
maximum wiring resistance 20 Ohm 2 wires Cu 10
20 Ohm 2 wires Ni 100
20 Ohm 2 wires Pt 100
20 Ohm 3 wires Cu 10
20 Ohm 3 wires Ni 100
20 Ohm 3 wires Pt 100
200 Ohm 2 wires Ni 1000
200 Ohm 2 wires Pt 1000
200 Ohm 3 wires Ni 1000
200 Ohm 3 wires Pt 1000
50 Ohm 4 wires Cu 10
50 Ohm 4 wires Ni 100
50 Ohm 4 wires Pt 100
500 Ohm 4 wires Ni 1000
500 Ohm 4 wires Pt 1000
measurement error +/- 0.7 °C Ni 1000 25 °C
+/- 1.3 °C Ni 1000 0...60 °C
+/- 2 °C Pt 100 0...60 °C
+/- 2 °C Pt 1000 0...60 °C
+/- 2.1 °C Ni 100 25 °C
+/- 2.1 °C Pt 100 25 °C
+/- 2.1 °C Pt 1000 25 °C
+/- 2.7 °C thermocouple U 25 °C
+/- 2.8 °C thermocouple J 25 °C
+/- 3 °C Ni 100 0...60 °C
+/- 3 °C thermocouple L 25 °C
+/- 3.2 °C thermocouple R 25 °C
+/- 3.2 °C thermocouple S 25 °C
+/- 3.5 °C thermocouple B 25 °C
+/- 3.7 °C thermocouple E 25 °C
+/- 3.7 °C thermocouple K 25 °C
+/- 3.7 °C thermocouple N 25 °C
+/- 3.7 °C thermocouple T 25 °C
+/- 4 °C Cu 10 0...60 °C
+/- 4 °C Cu 10 25 °C
+/- 4.5 °C thermocouple J 0...60 °C
+/- 4.5 °C thermocouple L 0...60 °C
+/- 4.5 °C thermocouple R 0...60 °C
+/- 4.5 °C thermocouple S 0...60 °C
+/- 4.5 °C thermocouple U 0...60 °C
+/- 5 °C thermocouple B 0...60 °C
+/- 5 °C thermocouple E 0...60 °C
+/- 5 °C thermocouple K 0...60 °C
+/- 5 °C thermocouple N 0...60 °C
+/- 5 °C thermocouple T 0...60 °C
<= 0.15 % of full scale +/- 1.28 V 0...60 °C
<= 0.15 % of full scale +/- 160 mV 0...60 °C
<= 0.15 % of full scale +/- 320 mV 0...60 °C
<= 0.15 % of full scale +/- 40 mV 0...60 °C
<= 0.15 % of full scale +/- 640 mV 0...60 °C
<= 0.15 % of full scale +/- 80 mV 0...60 °C
<= 0.2 % of full scale 400 Ohm 0...60 °C
<= 0.2 % of full scale 4000 Ohm 0...60 °C
0.05 % of full scale +/- 1.28 V 25 °C
0.05 % of full scale +/- 160 mV 25 °C
0.05 % of full scale +/- 320 mV 25 °C
0.05 % of full scale +/- 40 mV 25 °C
0.05 % of full scale +/- 640 mV 25 °C
0.05 % of full scale +/- 80 mV 25 °C
0.12 % of full scale 400 Ohm 25 °C
0.12 % of full scale 4000 Ohm 25 °C
Isolation between channels Isolated
Measurement resolution 0.1 °C Cu 10
0.1 °C Ni 100
0.1 °C Ni 1000
0.1 °C Pt 100
0.1 °C Pt 1000
0.1 °C thermocouple B
0.1 °C thermocouple E
0.1 °C thermocouple J
0.1 °C thermocouple K
0.1 °C thermocouple L
0.1 °C thermocouple N
0.1 °C thermocouple R
0.1 °C thermocouple S
0.1 °C thermocouple T
0.1 °C thermocouple U
1280/2exp14 mV +/- 1.28 V
160/2exp14 mV +/- 160 mV
320/2exp14 mV +/- 320 mV
40/2exp14 mV +/- 40 mV
12.5 mOhm 400 Ohm
125 mOhm 4000 Ohm
640/2exp14 mV +/- 640 mV
80/2exp14 mV +/- 80 mV
Nominal read cycle time 400 ms with temperature probe
200 ms with thermocouple
electrical connection 40 ways 1 connector
Permitted overload on inputs +/- 7.5 V +/- 1.28 V
+/- 7.5 V +/- 160 mV
+/- 7.5 V +/- 320 mV
+/- 7.5 V +/- 40 mV
+/- 7.5 V +/- 640 mV
+/- 7.5 V +/- 80 mV
Isolation voltage 1400 V DC between channels and bus
750 V DC between channels
750 V DC between channels and ground
Recalibration Internal
Shock resistance 30 gn
Status led 1 LED (green) RUN
1 LED per channel (green) channel diagnostic
1 LED (red) ERR
1 LED (red) I/O
Environment
Ambient air temp for storage/transportation -40…85 °C
Directives 2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
ip degree of protection IP20
operating altitude 0...2000 m
2000...5000 m with derating factor
Range of product Modicon X80
ambient air temperature for operation 0…60 °C
standards EN 61131-2
EN 61000-6-4
EN 61000-6-2
EN 61010-2-201
relative humidity 5…95 % at 55 °C without condensation
vibration resistance 3 gn
Recently viewed
454,72 €
454,72 € incl. VAT
Expected in 2-4 weeks