Main
product specific application
For severe environments
Complementary
Analogue output resolution
16 bits
Product certifications
Merchant Navy
ATEX
CE
CSA
EAC
RCM
IEC-Ex
UL
mtbf reliability
1500000 H
Product or component type
Analog output module
Common mode rejection
80 dB
Detection type
Open circuit 4...20 mA
Short circuit 0...20 mA
Analogue output number
8
Analogue output type
Current: 0...20 mA
Current: 4...20 mA
Load impedance ohmic
<= 350 Ohm 0...20 mA
<= 350 Ohm 4...20 mA
Fallback mode
Configurable
Predefined
temperature drift
45 ppm/°C 0...20 mA
45 ppm/°C 4...20 mA
Net weight
0.15 kg
Maximum conversion value
0...21 mA 0...20 mA
0...21 mA 4...20 mA
measurement error
<= 0.45 % of full scale - 25...70 °C
0.1 % of full scale 25 °C
Isolation between channels
Non isolated
Minimum crosstalk attenuation
80 dB
Power consumption in w
3.6 W 24 V DC typical
3.9 W 24 V DC maximum
0.35 W 3.3 V DC typical
0.48 W 3.3 V DC maximum
electrical connection
20 ways 1 connector
Isolation voltage
1400 V DC between channels and ground
1400 V DC between channels and bus
Shock resistance
30 gn
conversion time
<= 4 ms
Status led
1 LED (green) RUN
1 LED per channel (green) channel diagnostic
1 LED (red) ERR
1 LED (red) I/O
Supply
Internal power supply via rack
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP20
operating altitude
0...2000 m
2000...5000 m with derating factor
Range of product
Modicon X80
ambient air temperature for operation
-25…70 °C
Environmental characteristics
Gas resistant class Gx
Gas resistant class 3C4
Dust resistant class 3S4
Sand resistant class 3S4
Salt resistant level 2
Mold growth resistant class 3B2
Fungal spore resistant class 3B2
Hazardous location class I division 2
standards
EN 61131-2
EN 61000-6-4
EN 61000-6-2
EN 61010-2-201
relative humidity
5…95 % at 55 °C without condensation
vibration resistance
3 gn
protective treatment
Conformal coating