Main
Analogue input resolution
12 bits 0...20 mA
12 bits 0...5 V
12 bits 1...5 V
12 bits 4...20 mA
13 bits 0...10 V
14 bits +/- 10 V
Input level
High level
product specific application
For severe environments
type of filter
First order digital filtering by firmware
Complementary
Analogue output resolution
11 bits, 0...20 mA
11 bits, 4...20 mA
12 bits, +/- 10 V
Product certifications
CE
RCM
CSA
EAC
Merchant Navy
UL
ATEX
IEC-Ex
mtbf reliability
1400000 H
Product or component type
Mixed analog I/O module
Analogue input number
4
Common mode rejection
80 dB
Analogue input type
Current 0...20 mA
Current 4...20 mA
Voltage +/- 10 V
Voltage 0...10 V
Voltage 0...5 V
Voltage 1...5 V
Fast read cycle time
1 ms + 1 ms x number of channels used
Analogue output number
2
Analogue output type
Current: 0...20 mA
Current: 4...20 mA
Voltage: +/- 10 V
Fallback mode
Predefined
Configurable
temperature drift
100 ppm/°C +/- 10 V output
100 ppm/°C 0...20 mA output
100 ppm/°C 4...20 mA output
30 ppm/°C +/- 10 V input
30 ppm/°C 0...10 V input
30 ppm/°C 0...5 V input
30 ppm/°C 1...5 V input
50 ppm/°C 0...20 mA input
50 ppm/°C 4...20 mA input
Net weight
0.155 kg
Maximum conversion value
+/- 11.25 V +/- 10 V output
+/- 11.25 V +/- 10 V input
0...30 mA 0...20 mA input
0...30 mA 4...20 mA input
+/- 11.25 V 0...10 V input
+/- 11.25 V 0...5 V input
+/- 11.25 V 1...5 V input
0...24 mA 0...20 mA output
0...24 mA 4...20 mA output
measurement error
0.25 % of full scale 0...20 mA 25 °C output
0.25 % of full scale 4...20 mA 25 °C output
0.25 % of full scale +/- 10 V 25 °C output
0.25 % of full scale +/- 10 V 25 °C input
0.25 % of full scale 0...10 V 25 °C input
0.25 % of full scale 0...5 V 25 °C input
0.25 % of full scale 1...5 V 25 °C input
0.35 % of full scale 0...20 mA 25 °C input
0.35 % of full scale 4...20 mA 25 °C input
<= 0.4 % of full scale +/- 10 V - 25...70 °C input
<= 0.4 % of full scale 0...10 V - 25...70 °C input
<= 0.4 % of full scale 0...5 V - 25...70 °C input
<= 0.4 % of full scale 1...5 V - 25...70 °C input
<= 0.6 % of full scale 0...20 mA - 25...70 °C input
<= 0.6 % of full scale 4...20 mA - 25...70 °C input
<= 0.8 % of full scale +/- 10 V - 25...70 °C output
<= 0.8 % of full scale 0...20 mA - 25...70 °C output
<= 0.8 % of full scale 4...20 mA - 25...70 °C output
Isolation between channels
Non isolated
input impedance
250 Ohm
Minimum crosstalk attenuation
70 dB
Nominal read cycle time
5 ms for 4 channels
Power consumption in w
2.6 W 24 V DC typical
3.2 W 24 V DC maximum
0.35 W 3.3 V DC typical
0.48 W 3.3 V DC maximum
electrical connection
20 ways 1 connector
Permitted overload on inputs
+/- 30 mA 0...20 mA
+/- 30 mA 4...20 mA
+/- 30 V +/- 10 V
+/- 30 V 0...10 V
+/- 30 V 0...5 V
+/- 30 V 1...5 V
Output level
High level
Precision of internal conversion resistor
0.1 % - 15 ppm/°C
Isolation voltage
1400 V DC between channels and ground
1400 V DC between channels and bus
750 V DC between group of I/O channels
Recalibration
Internal on inputs
Factory calibrated on outputs
Shock resistance
30 gn
conversion time
<= 2 ms
Status led
1 LED (green) RUN
1 LED per channel (green) channel diagnostic
1 LED (red) ERR
1 LED (red) I/O
Environment
Ambient air temp for storage/transportation
-40…85 °C
Directives
2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
ip degree of protection
IP20
operating altitude
0...2000 m
2000...5000 m with derating factor
Range of product
Modicon X80
ambient air temperature for operation
-25…70 °C
Environmental characteristics
Gas resistant class Gx
Gas resistant class 3C4
Dust resistant class 3S4
Sand resistant class 3S4
Salt resistant level 2
Mold growth resistant class 3B2
Fungal spore resistant class 3B2
Hazardous location
standards
EN/IEC 61010-2-201
EN/IEC 61131-2
UL 61010-2-201
CSA C22.2 No 61010-2-201
relative humidity
5…95 % at 55 °C without condensation
vibration resistance
3 gn
protective treatment
Conformal coating