BMXAMM0600 - Analog non isolated high level input and output module, Modicon X80, 4 inputs, 2 outputs, 0 to 20mA / 4 to 20mA, 10V positive or negative - Schneider Electric

Expected in 2-4 weeks
BMXAMM0600 - Analog non isolated high level input and output module, Modicon X80, 4 inputs, 2 outputs, 0 to 20mA / 4 to 20mA, 10V positive or negative - Schneider Electric - Analog non isolated high level input and output module, Modicon X80, 4 inputs, 2 outputs, 0 to 20mA / 4 to 20mA, 10V positive or negative - Schneider Electric - 0
BMXAMM0600 - Analog non isolated high level input and output module, Modicon X80, 4 inputs, 2 outputs, 0 to 20mA / 4 to 20mA, 10V positive or negative - Schneider Electric
539,83 € excl. VAT
658,59 € incl. VAT
Text About:
Analog non isolated high level input and output module, Modicon X80, 4 inputs, 2 outputs, 0 to 20mA / 4 to 20mA, 10V positive or negative - Schneider Electric
658,59 €
SPECIFICATIONS
Main
Analogue input resolution 12 bits 0...20 mA
12 bits 0...5 V
12 bits 1...5 V
12 bits 4...20 mA
13 bits 0...10 V
14 bits +/- 10 V
Input level High level
type of filter First order digital filtering by firmware
Complementary
Analogue output resolution 11 bits, 0...20 mA
11 bits, 4...20 mA
12 bits, +/- 10 V
Product certifications CE
RCM
CSA
EAC
Merchant Navy
UL
mtbf reliability 1400000 H
Product or component type Mixed analog I/O module
Current consumption 240 mA at 3.3 V DC
Analogue input number 4
Common mode rejection 80 dB
Analogue input type Current 0...20 mA
Current 4...20 mA
Voltage +/- 10 V
Voltage 0...10 V
Voltage 0...5 V
Voltage 1...5 V
Fast read cycle time 1 ms + 1 ms x number of channels used
Analogue output number 2
Analogue output type Current: 0...20 mA
Current: 4...20 mA
Voltage: +/- 10 V
Fallback mode Predefined
Configurable
temperature drift 100 ppm/°C +/- 10 V output
100 ppm/°C 0...20 mA output
100 ppm/°C 4...20 mA output
30 ppm/°C +/- 10 V input
30 ppm/°C 0...10 V input
30 ppm/°C 0...5 V input
30 ppm/°C 1...5 V input
50 ppm/°C 0...20 mA input
50 ppm/°C 4...20 mA input
Net weight 0.155 kg
Maximum conversion value +/- 11.25 V +/- 10 V output
+/- 11.25 V +/- 10 V input
0...30 mA 0...20 mA input
0...30 mA 4...20 mA input
+/- 11.25 V 0...10 V input
+/- 11.25 V 0...5 V input
+/- 11.25 V 1...5 V input
0...24 mA 0...20 mA output
0...24 mA 4...20 mA output
measurement error 0.25 % of full scale 0...20 mA 25 °C output
0.25 % of full scale 4...20 mA 25 °C output
<= 0.35 % of full scale +/- 10 V 0...60 °C input
<= 0.35 % of full scale 0...10 V 0...60 °C input
<= 0.35 % of full scale 0...5 V 0...60 °C input
<= 0.35 % of full scale 1...5 V 0...60 °C input
<= 0.5 % of full scale 0...20 mA 0...60 °C input
<= 0.5 % of full scale 4...20 mA 0...60 °C input
<= 0.6 % of full scale +/- 10 V 0...60 °C output
<= 0.6 % of full scale 0...20 mA 0...60 °C output
<= 0.6 % of full scale 4...20 mA 0...60 °C output
0.25 % of full scale +/- 10 V 25 °C output
0.25 % of full scale +/- 10 V 25 °C input
0.25 % of full scale 0...10 V 25 °C input
0.25 % of full scale 0...5 V 25 °C input
0.25 % of full scale 1...5 V 25 °C input
0.35 % of full scale 0...20 mA 25 °C input
0.35 % of full scale 4...20 mA 25 °C
Isolation between channels Non isolated
input impedance 250 Ohm
Minimum crosstalk attenuation 70 dB
Nominal read cycle time 5 ms for 4 channels
Power consumption in w 2.6 W 24 V DC typical
3.2 W 24 V DC maximum
0.35 W 3.3 V DC typical
0.48 W 3.3 V DC maximum
electrical connection 20 ways 1 connector
Permitted overload on inputs +/- 30 mA 0...20 mA
+/- 30 mA 4...20 mA
+/- 30 V +/- 10 V
+/- 30 V 0...10 V
+/- 30 V 0...5 V
+/- 30 V 1...5 V
Output level High level
Precision of internal conversion resistor 0.1 % - 15 ppm/°C
Isolation voltage 1400 V DC between channels and ground
1400 V DC between channels and bus
750 V DC between group of I/O channels
Recalibration Factory calibrated on outputs
Internal on inputs
Shock resistance 30 gn
conversion time <= 2 ms
Status led 1 LED (green) RUN
1 LED per channel (green) channel diagnostic
1 LED (red) ERR
1 LED (red) I/O
Environment
Ambient air temp for storage/transportation -40…85 °C
Directives 2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
ip degree of protection IP20
operating altitude 0...2000 m
2000...5000 m with derating factor
Range of product Modicon X80
ambient air temperature for operation 0…60 °C
standards EN/IEC 61010-2-201
EN/IEC 61131-2
UL 61010-2-201
CSA C22.2 No 61010-2-201
relative humidity 5…95 % at 55 °C without condensation
vibration resistance 3 gn