Main
Analogue input resolution
16 bits
Input level
High level
product specific application
For severe environments
type of filter
First order digital filtering
Complementary
Analog/digital conversion
24 bits
Product certifications
CE
RCM
CSA
EAC
Merchant Navy
UL
ATEX
IEC-Ex
mtbf reliability
1200000 H
Product or component type
Analog input module
Digital value format
- 32768 to + 32767 in maximum user scale
+/- 10000 by default
Analogue input number
4
Common mode rejection
90 dB
Analogue input type
Current +/- 20 mA
Current 0...20 mA
Current 4...20 mA
Voltage +/- 10 V
Voltage +/- 5 V
Voltage 0...10 V
Voltage 0...5 V
Voltage 1...5 V
Fast read cycle time
1 ms + 1 ms x number of channels used
temperature drift
15 ppm/°C +/- 10 V
15 ppm/°C +/- 5 V
15 ppm/°C 0...10 V
15 ppm/°C 0...5 V
15 ppm/°C 1...5 V
30 ppm/°C +/- 20 mA
30 ppm/°C 0...20 mA
30 ppm/°C 4...20 mA
Net weight
0.143 kg
Maximum conversion value
+/- 11.4 V +/- 10 V
+/- 11.4 V +/- 5 V
+/- 11.4 V 0...10 V
+/- 11.4 V 0...5 V
+/- 11.4 V 1...5 V
0...30 mA +/- 20 mA
0...30 mA 0...20 mA
0...30 mA 4...20 mA
measurement error
0.075 % of full scale +/- 10 V 25 °C
0.075 % of full scale +/- 5 V 25 °C
0.075 % of full scale 0...10 V 25 °C
0.075 % of full scale 0...5 V 25 °C
0.075 % of full scale 1...5 V 25 °C
0.15 % of full scale +/- 20 mA 25 °C
0.15 % of full scale 0...20 mA 25 °C
0.15 % of full scale 4...20 mA 25 °C
<= 0.2 % of full scale +/- 10 V - 25...70 °C
<= 0.2 % of full scale +/- 5 V - 25...70 °C
<= 0.2 % of full scale 0...10 V - 25...70 °C
<= 0.2 % of full scale 0...5 V - 25...70 °C
<= 0.2 % of full scale 1...5 V - 25...70 °C
<= 0.55 % of full scale +/- 20 mA - 25...70 °C
<= 0.55 % of full scale 0...20 mA - 25...70 °C
<= 0.55 % of full scale 4...20 mA - 25...70 °C
Isolation between channels
Isolated
input impedance
10 MOhm in voltage mode
250 Ohm + 3.6...50 Ohm internal protective resistor in current mode
Measurement resolution
0.35 mV +/- 10 V
0.35 mV +/- 5 V
0.35 mV 0...10 V
0.35 mV 0...5 V
0.35 mV 1...5 V
0.92 µA +/- 20 mA
0.92 µA 0...20 mA
0.92 µA 4...20 mA
Minimum crosstalk attenuation
80 dB
Nominal read cycle time
5 ms for 4 channels
Power consumption in w
0.82 W 24 V DC typical
1.30 W 24 V DC maximum
0.32 W 3.3 V DC typical
0.48 W 3.3 V DC maximum
electrical connection
20 ways 1 connector
Permitted overload on inputs
+/- 30 V +/- 10 V
+/- 30 V +/- 5 V
+/- 30 V 0...10 V
+/- 30 V 0...5 V
+/- 30 V 1...5 V
+/- 90 mA +/- 20 mA
+/- 90 mA 0...20 mA
+/- 90 mA 4...20 mA
Precision of internal conversion resistor
0.1 % - 15 ppm/°C
Isolation voltage
300 V DC between channels
1400 V DC between channels and ground
1400 V DC between channels and bus
Recalibration
Internal
Shock resistance
30 gn
Status led
1 LED (green) RUN
1 LED per channel (green) channel diagnostic
1 LED (red) ERR
1 LED (red) I/O
Environment
Ambient air temp for storage/transportation
-40…85 °C
Directives
2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
ip degree of protection
IP20
operating altitude
0...2000 m
2000...5000 m with derating factor
Range of product
Modicon X80
ambient air temperature for operation
-25…70 °C
Environmental characteristics
Gas resistant class Gx
Gas resistant class 3C4
Dust resistant class 3S4
Sand resistant class 3S4
Salt resistant level 2
Mold growth resistant class 3B2
Fungal spore resistant class 3B2
Hazardous location
standards
EN/IEC 61010-2-201
EN/IEC 61131-2
UL 61010-2-201
CSA C22.2 No 61010-2-201
relative humidity
5…95 % at 55 °C without condensation
vibration resistance
3 gn
protective treatment
Conformal coating