Complementary
control channels
Programmable loops
Application structure
1 periodic fast task
2 auxiliary tasks
1 cyclic/periodic master task
64 event tasks
Product certifications
CE
UL
CSA
RCM
EAC
Merchant Navy
mtbf reliability
775000 H
Product or component type
Processor module
application specific I/O
Accurate time stamping
Motion control
Counter
HART
SSI encoder
Serial link
Current consumption
270 mA at 24 V DC
Communication module processor capacity
2 Ethernet communication module
8 AS-Interface module
marking
CE
Local i/o processor capacity (analog)
256 I/O
Memory description
Integrated RAM, 4 MB for program
Integrated RAM, 384 kB for data
Expandable flash, 4 GB for data storage
Integrated RAM, 10 kB for system memory
Net weight
0.849 kg
number of instructions per ms
7.5 Kinst/ms 65 % Boolean + 35 % fixed arithmetic
10 Kinst/ms 100 % Boolean
Local i/o processor capacity (discrete)
1024 I/O
Communication service
DIO scanner
Integrated connection type
1 Ethernet TCP/IP for service port
2 Ethernet TCP/IP for device network
USB type mini B
Number of distributed equipment
64
Number of application specific channel (local rack)
36
Number of racks
4
Shock resistance
30 gn
Status led
1 LED (green) processor running (RUN)
1 LED (red) processor or system fault (ERR)
1 LED (red) I/O module fault (I/O)
1 LED (green) download in progress (DL)
1 LED (red) memory card or CPU flash fault (BACKUP)
1 LED (green/red) ETH MS (Ethernet port configuration status)
1 LED (green/red) Eth NS (Ethernet network status)
Supply
Internal power supply via rack
checks
Process control
Environment
Ambient air temp for storage/transportation
-40…85 °C
Directives
2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
ip degree of protection
IP20
operating altitude
0...2000 m
2000...5000 m with derating factor
Range of product
Modicon M580
ambient air temperature for operation
0…60 °C
Environmental characteristics
Hazardous location class I division 2
standards
EN 61131-2
EN/IEC 61010-2-201
UL 61010-2-201
CSA C22.2 No 61010-2-201
IACS E10
EN/IEC 61000-6-5, interface type 1 and type 2
EN/IEC 61850-3, location G
relative humidity
5…95 % at 55 °C without condensation
vibration resistance
3 gn