Complementary
4 quadrant operation possible
True
with safety function safe brake management (sbc/sbt)
True
Product certifications
UL
CSA
TÜV
with safety function safe operating stop (sos)
False
data formats
8 bits, configurable odd, even or no parity for Modbus serial
Handle front plate colour
1205 mm
Product or component type
Variable speed drive
[us] rated supply voltage
380...480 V - 15...10 %
Assembly style
Enclosed
with safety function safe programmable logic
False
noise level
69.9 dB
marking
CE
Quantity per set
1
with safety function safe stop 1 (ss1)
True
Device application
Industrial application
Asynchronous motor control profile
Constant torque standard
Variable torque standard
Optimized torque mode
width (w)
320 mm
isolation
Between power and control terminals
network frequency
50...60 Hz
switching frequency
1...8 kHz adjustable
2.5...8 kHz with derating factor
with safety function safely limited speed (sls)
True
Brake chopper integrated
True
Local signalling
Local diagnostic: 3 LEDs (mono/dual colour)
5 LEDs (dual colour)
2 LEDs (dual colour)
1 LED (red)
motor slip compensation
Adjustable
Automatic whatever the load
Can be suppressed
Not available in permanent magnet motor law
Mounting mode
Wall mount
Braking to standstill
By DC injection
Discrete input number
10
Net weight
104 kg
physical interface
Ethernet
2-wire RS 485
Base load current at low overload
302.0 A
base load current at high overload
250.0 A
Operating position
Vertical +/- 10 degree
communication port protocol
Ethernet IP/Modbus TCP
Modbus
Motor power hp
250.0 hp for normal duty
200.0 hp for heavy duty
connector type
2 RJ45
1 RJ45
depth
393 mm
line current
284.0 A at 380 V (normal duty)
237.0 A at 380 V (heavy duty)
262.0 A at 480 V (normal duty)
213.0 A at 480 V (heavy duty)
continuous output current
302 A at 4 kHz for normal duty
250 A at 4 kHz for heavy duty
maximum transient current
362 A during 60 s (normal duty)
375 A during 60 s (heavy duty)
Pollution degree
2
electrical connection
Line side: screw terminal 2 x 95...3 x 120 mm²/2 x AWG 3/0...2 x 300 kcmil
DC bus: screw terminal 0.5...1.5 mm²/AWG 20...AWG 16
Control: screw terminal 0.5...1.5 mm²/AWG 20...AWG 16
Network number of phases
3 phases
Single phase
nominal switching frequency
2.5 kHz
maximum output frequency
599 Hz
Product destination
Synchronous motors
Asynchronous motors
Maximum input current
284.0 A
Maximum output voltage
480.0 V
Shock resistance
6 gn for 11 ms conforming to IEC 60068-2-27
Method of access
Slave Modbus TCP
synchronous motor control profile
Permanent magnet motor
Synchronous reluctance motor
apparent power
201.3 kVA at 380...480 V (normal duty)
161.4 kVA at 380...480 V (heavy duty)
number of addresses
1…247 for Modbus serial
acceleration and deceleration ramps
Linear adjustable separately from 0.01...9999 s
S, U or customized
Protection type
Thermal protection: motor
Safe torque off: motor
Motor phase break: motor
Thermal protection: drive
Safe torque off: drive
Overheating: drive
Overcurrent between output phases and earth: drive
Overload of output voltage: drive
Short-circuit protection: drive
Motor phase break: drive
Overvoltages on the DC bus: drive
Line supply overvoltage: drive
Line supply undervoltage: drive
Line supply phase loss: drive
Overspeed: drive
Break on the control circuit: drive
relay output type
Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles
Configurable relay logic R2: sequence relay NO electrical durability 1000000 cycles
Configurable relay logic R3: sequence relay NO electrical durability 1000000 cycles
Transmission rate
10/100 Mbit/s for Ethernet IP/Modbus TCP
4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial
Prospective line isc
50 kA
transmission frame
RTU
Relative symmetric network frequency tolerance
5 %
Type of polarization
No impedance for Modbus serial
With safety function safe direction (sdi)
False
With safety function safe position (sp)
False
With safety function safe speed monitor (ssm)
False
With safety function safe torque off (sto)
True
With safety function safely limited position (slp)
False
With sft fct safe stop 2 (ss2)
False
Environment
Ambient air temp for storage/transportation
-25…70 °C
Environmental class (during operation)
Class 3C3 according to IEC 60721-3-3
Class 3S3 according to IEC 60721-3-3
ip degree of protection
IP21
Range of product
Altivar Process ATV900
ambient air temperature for operation
-15…50 °C (without derating)
50…60 °C (with derating factor)
electromagnetic compatibility
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Environmental characteristics
Chemical pollution resistance class 3C3 conforming to EN/IEC 60721-3-3
Dust pollution resistance class 3S3 conforming to EN/IEC 60721-3-3
Maximum acceleration under shock impact (during operation)
150 m/s² at 11 ms
overvoltage category
III
standards
UL 508C
EN/IEC 61800-3
EN/IEC 61800-5-1
IEC 61000-3-12
IEC 60721-3
IEC 61508
IEC 13849-1
relative humidity
5…95 % without condensation conforming to IEC 60068-2-3
Maximum acceleration under vibrational stress (during operation)
10 m/s² at 13...200 Hz
Permitted relative humidity (during operation)
Class 3K5 according to EN 60721-3
Maximum thdi
<48 % full load conforming to IEC 61000-3-12
Maximum deflection under vibratory load (during operation)
1.5 mm at 2...13 Hz
Regulation loop
Adjustable PID regulator
vibration resistance
1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6
1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
insulation resistance
> 1 MOhm 500 V DC for 1 minute to earth