Complementary
Accuracy
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
maximum switching current
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC
Product certifications
TÜV
CSA
ATEX zone 2/22
ATEX INERIS
RoHS
data formats
8 bits, configurable odd, even or no parity
Handle front plate colour
2350 mm
Product or component type
Variable speed drive
[us] rated supply voltage
380...440 V - 15...10 %
minimum switching current
Relay output R1, R2, R3: 5 mA at 24 V DC
noise level
69 dB
marking
CE
Quantity per set
1
Analogue input number
3
Analogue input type
AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm, resolution 12 bits
AI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits
AI2 voltage analog input: - 10...10 V DC, impedance: 31.5 kOhm, resolution 12 bits
refresh time
Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
Analogue output number
2
Asynchronous motor control profile
Variable torque standard
Constant torque standard
Constant torque standard
Discrete input logic
Positive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1)
Negative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1)
output voltage
<= power supply voltage
width (w)
400 mm
Analogue output type
Software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits
Software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits
Software-configurable current DQ-, DQ+: 30 V DC
Software-configurable current DQ-, DQ+: 100 mA
Discrete input type
DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
isolation
Between power and control terminals
switching frequency
2...8 kHz adjustable
2.5...8 kHz with derating factor
Local signalling
3 LEDs (dual colour) for embedded communication status
4 LEDs (dual colour) for communication module status
1 LED (red) for presence of voltage
3 LEDs for local diagnostic
motor slip compensation
Not available in permanent magnet motor law
Can be suppressed
Automatic whatever the load
Can be suppressed
Mounting mode
Floor-standing
Braking to standstill
By DC injection
Discrete input number
8
Net weight
310 kg
physical interface
Ethernet
2-wire RS 485
Discrete output type
Relay outputs R1A, R1B, R1C 250 V AC 3000 mA
Relay outputs R1A, R1B, R1C 30 V DC 3000 mA
Relay outputs R2A, R2C 250 V AC 5000 mA
Relay outputs R2A, R2C 30 V DC 5000 mA
Relay outputs R3A, R3C 250 V AC 5000 mA
Relay outputs R3A, R3C 30 V DC 5000 mA
Operating position
Vertical +/- 10 degree
communication port protocol
Modbus serial
Ethernet
Ethernet
connector type
RJ45 (on the remote graphic terminal) for Modbus serial
RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP
depth
669 mm
line current
210 A at 400 V (heavy duty)
179 A at 380 V (normal duty)
244 A at 380 V (heavy duty)
207 A at 400 V (normal duty)
power dissipation in w
2010 W, switching frequency 2.5 kHz (heavy duty)
3150 W, switching frequency 2.5 kHz (normal duty)
continuous output current
250 A at 2.5 kHz for normal duty
211 A at 2.5 kHz for heavy duty
Motor power range ac-3
110…220 kW at 480…500 V 3 phases
110…220 kW at 380…440 V 3 phases
maximum transient current
275 A during 60 s (normal duty)
317 A during 60 s (heavy duty)
Permissible temporary current boost
1.5 x In during 60 s (heavy duty)
1.1 x In during 60 s (normal duty)
Pollution degree
3
electrical connection
Line side: M12 bar - 1 cables 3 x 150 mm² minimum per phase (normal duty)
Line side: M12 bar - 2 cables 3 x 70 mm² minimum per phase (normal duty)
Line side: M12 bar - 1 cables 3 x 185 mm² maximum per phase (normal duty)
Line side: M12 bar - 2 cables 3 x 120 mm² maximum per phase (normal duty)
Motor: M12 bar - 1 cables 3 x 120 mm² minimum per phase (normal duty)
Motor: M12 bar - 2 cables 3 x 50 mm² minimum per phase (normal duty)
Motor: M12 bar - 2 cables 3 x 185 mm² maximum per phase (normal duty)
Line side: M12 bar - 1 cables 3 x 150 mm² minimum per phase (heavy duty)
Line side: M12 bar - 2 cables 3 x 70 mm² minimum per phase (heavy duty)
Line side: M12 bar - 1 cables 3 x 185 mm² maximum per phase (heavy duty)
Line side: M12 bar - 2 cables 3 x 120 mm² maximum per phase (heavy duty)
Motor: M12 bar - 1 cables 3 x 95 mm² minimum per phase (heavy duty)
Motor: M12 bar - 2 cables 3 x 185 mm² maximum per phase (heavy duty)
Control: removable screw terminals 0.5...1.5 mm²
linearity error
AO1, AO2: +/- 0.2 % for analog output
AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input
Network number of phases
3 phases
nominal switching frequency
2.5 kHz
Enclosure mounting
Floor-standing
maximum output frequency
500 kHz
Exchange mode
Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Input compatibility
DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68
STOA, STOB: discrete input level 1 PLC conforming to EN/IEC 61131-2
DI1...DI6: discrete input level 1 PLC conforming to EN/IEC 61131-2
Product destination
Asynchronous motors
Synchronous motors
Maximum input current
244.0 A
Shock resistance
15 gn for 11 ms conforming to IEC 60068-2-27
Method of access
Slave Modbus TCP
synchronous motor control profile
Synchronous reluctance motor
Permanent magnet motor
Supply frequency
50...60 Hz - 5...5 %
apparent power
160 kVA at 440 V (normal duty)
136 kVA at 440 V (heavy duty)
number of addresses
1…247 for Modbus serial
Supply
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
Internal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection
External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection
variable speed drive application selection
Food and beverage processing other application
Mining mineral and metal fan
Mining mineral and metal pump
Oil and gas fan
Water and waste water other application
Building - HVAC screw compressor
Food and beverage processing pump
Food and beverage processing fan
Food and beverage processing atomization
Oil and gas electro submersible pump (ESP)
Oil and gas water injection pump
Oil and gas jet fuel pump
Oil and gas compressor for refinery
Water and waste water centrifuge pump
Water and waste water positive displacement pump
Water and waste water electro submersible pump (ESP)
Water and waste water screw pump
Water and waste water lobe compressor
Water and waste water screw compressor
Water and waste water compressor centrifugal
Water and waste water fan
Water and waste water conveyor
Water and waste water mixer
Building - HVAC compressor centrifugal
acceleration and deceleration ramps
Linear adjustable separately from 0.01...9999 s
Protection type
Safe torque off: motor
Motor phase break: motor
Thermal protection: drive
Safe torque off: drive
Overheating: drive
Overcurrent between output phases and earth: drive
Overload of output voltage: drive
Short-circuit protection: drive
Motor phase break: drive
Overvoltages on the DC bus: drive
Line supply overvoltage: drive
Line supply undervoltage: drive
Line supply phase loss: drive
Overspeed: drive
Break on the control circuit: drive
Thermal protection: motor
Option card
Slot A: communication module, PROFINET
Slot A: communication module, DeviceNet
Slot A: communication module, Modbus TCP/EtherNet/IP
Slot A: communication module, CANopen daisy chain RJ45
Slot A: communication module, CANopen SUB-D 9
Slot A: communication module, CANopen screw terminals
Slot A/slot B: digital and analog I/O extension module
Slot A/slot B: output relay extension module
Slot A: communication module, Ethernet IP/Modbus TCP/MD-Link
Communication module, BACnet MS/TP
Communication module, Ethernet Powerlink
Slot A: communication module, Profibus DP V1
relay output type
Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles
Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles
Transmission rate
10, 100 Mbits
4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Type of cooling
Forced convection
frequency resolution
Analog input: 0.012/50 Hz
Display unit: 0.1 Hz
Prospective line isc
50 kA
transmission frame
RTU
Relay output number
3
Sampling duration
5 ms +/- 1 ms (DI5, DI6) - discrete input
5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input
10 ms +/- 1 ms (AO1) - analog output
2 ms +/- 0.5 ms (DI1...DI4) - discrete input
Speed drive output frequency
0.1…500 Hz
Type of polarization
No impedance
Volume of cooling air
720 m3/h