All categories
Compare Cart

ATV650C11N4F - Variable speed drive, Altivar Process ATV600, ATV650, 110 kW, 380...440 V, IP54, disconnect switch - Schneider Electric

Expected in 2-4 weeks
ATV650C11N4F - Variable speed drive, Altivar Process ATV600, ATV650, 110 kW, 380...440 V, IP54, disconnect switch - Schneider Electric - Variable speed drive, Altivar Process ATV600, ATV650, 110 kW, 380...440 V, IP54, disconnect switch - Schneider Electric - 0
ATV650C11N4F - Variable speed drive, Altivar Process ATV600, ATV650, 110 kW, 380...440 V, IP54, disconnect switch - Schneider Electric
11 984,09 €
11 984,09 € incl. VAT
Text About:
Variable speed drive, Altivar Process ATV600, ATV650, 110 kW, 380...440 V, IP54, disconnect switch - Schneider Electric
11 984,09 €
SPECIFICATIONS
Main
Device short name ATV650
product specific application Process and utilities
Safety function STO (safe torque off) SIL 3
emc filter Integrated with 150 m conforming to EN/IEC 61800-3 category C3
motor power kW 110 kW (normal duty)
90 kW (heavy duty)
variant With disconnect switch
Complementary
Accuracy +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
maximum switching current Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC
Product certifications TÜV
CSA
ATEX zone 2/22
ATEX INERIS
RoHS
data formats 8 bits, configurable odd, even or no parity
Handle front plate colour 2350 mm
Product or component type Variable speed drive
[us] rated supply voltage 380...440 V - 15...10 %
minimum switching current Relay output R1, R2, R3: 5 mA at 24 V DC
noise level 69 dB
marking CE
Quantity per set 1
Analogue input number 3
Analogue input type AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm, resolution 12 bits
AI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits
AI2 voltage analog input: - 10...10 V DC, impedance: 31.5 kOhm, resolution 12 bits
refresh time Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
Analogue output number 2
Asynchronous motor control profile Optimized torque mode
Variable torque standard
Optimized torque mode
Discrete input logic Positive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1)
Negative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1)
output voltage <= power supply voltage
width (w) 400 mm
Analogue output type Software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits
Software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits
Software-configurable current DQ-, DQ+: 30 V DC
Software-configurable current DQ-, DQ+: 100 mA
Discrete input type DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
isolation Between power and control terminals
switching frequency 4...8 kHz with derating factor
2.5...8 kHz with derating factor
Local signalling 3 LEDs (dual colour) for embedded communication status
4 LEDs (dual colour) for communication module status
1 LED (red) for presence of voltage
3 LEDs for local diagnostic
motor slip compensation Not available in permanent magnet motor law
Can be suppressed
Adjustable
Adjustable
Mounting mode Floor-standing
Braking to standstill By DC injection
Discrete input number 8
Net weight 310 kg
physical interface Ethernet
2-wire RS 485
Discrete output type Relay outputs R1A, R1B, R1C 250 V AC 3000 mA
Relay outputs R1A, R1B, R1C 30 V DC 3000 mA
Relay outputs R2A, R2C 250 V AC 5000 mA
Relay outputs R2A, R2C 30 V DC 5000 mA
Relay outputs R3A, R3C 250 V AC 5000 mA
Relay outputs R3A, R3C 30 V DC 5000 mA
Operating position Vertical +/- 10 degree
communication port protocol Modbus serial
Ethernet
Modbus TCP
connector type RJ45 (on the remote graphic terminal) for Modbus serial
RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP
depth 669 mm
line current 179 A at 690 V (normal duty)
151 A at 500 V (heavy duty)
207 A at 690 V (heavy duty)
174 A at 400 V (normal duty)
power dissipation in w Forced convection: 136 W at 500 V, switching frequency 4 kHz
2530 W, switching frequency 2.5 kHz (normal duty)
continuous output current 211 A at 2.5 kHz for normal duty
173 A at 2.5 kHz for heavy duty
Motor power range ac-3 110…220 kW at 380…440 V 3 phases
maximum transient current 232 A during 60 s (normal duty)
260 A during 60 s (heavy duty)
Permissible temporary current boost 1.5 x In during 60 s (heavy duty)
1.1 x In during 60 s (normal duty)
Pollution degree 3
electrical connection Motor: screw terminal 4...10 mm²/AWG 12...AWG 8
Line side: screw terminal 4...10 mm²/AWG 12...AWG 8
Control: removable screw terminals 0.5...1.5 mm²
linearity error AO1, AO2: +/- 0.2 % for analog output
AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input
Network number of phases 3 phases
nominal switching frequency 2.5 kHz
Enclosure mounting Floor-standing
maximum output frequency 500 kHz
Exchange mode Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Input compatibility DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68
STOA, STOB: discrete input level 1 PLC conforming to EN/IEC 61131-2
DI1...DI6: discrete input level 1 PLC conforming to EN/IEC 61131-2
Product destination Asynchronous motors
Synchronous motors
Maximum input current 207.0 A
Shock resistance 15 gn for 11 ms conforming to IEC 60068-2-27
Method of access Slave Modbus TCP
synchronous motor control profile Synchronous reluctance motor
Permanent magnet motor
Supply frequency 50...60 Hz - 5...5 %
apparent power 136 kVA at 440 V (normal duty)
115 kVA at 440 V (heavy duty)
number of addresses 1…247 for Modbus serial
Supply Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
Internal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection
External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection
variable speed drive application selection Building - HVAC compressor centrifugal
acceleration and deceleration ramps S, U or customized
Linear adjustable separately from 0.01...9999 s
Protection type Safe torque off: motor
Motor phase break: motor
Thermal protection: drive
Safe torque off: drive
Overheating: drive
Overcurrent between output phases and earth: drive
Overload of output voltage: drive
Short-circuit protection: drive
Motor phase break: drive
Overvoltages on the DC bus: drive
Line supply overvoltage: drive
Line supply undervoltage: drive
Line supply phase loss: drive
Overspeed: drive
Break on the control circuit: drive
Thermal protection: motor
Option card Slot A: communication module, PROFINET
Slot A: communication module, DeviceNet
Slot A: communication module, Modbus TCP/EtherNet/IP
Slot A: communication module, CANopen daisy chain RJ45
Slot A: communication module, CANopen SUB-D 9
Slot A: communication module, CANopen screw terminals
Slot A/slot B: digital and analog I/O extension module
Slot A/slot B: output relay extension module
Slot A: communication module, Ethernet IP/Modbus TCP/MD-Link
Communication module, BACnet MS/TP
Communication module, Ethernet Powerlink
Slot A: communication module, Profibus DP V1
relay output type Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles
Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles
Transmission rate 10, 100 Mbits
4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Type of cooling Forced convection
frequency resolution Analog input: 0.012/50 Hz
Display unit: 0.1 Hz
Prospective line isc 50 kA
transmission frame RTU
Relay output number 3
Sampling duration 5 ms +/- 1 ms (DI5, DI6) - discrete input
5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input
10 ms +/- 1 ms (AO1) - analog output
2 ms +/- 0.5 ms (DI1...DI4) - discrete input
Speed drive output frequency 0.1…500 Hz
Type of polarization No impedance
Volume of cooling air 720 m3/h
Environment
Ambient air temp for storage/transportation -40…70 °C
ip degree of protection IP00 conforming to IEC 60529
IP20 (with kit VW3A9705) conforming to IEC 61800-5-1
IP20 (with kit VW3A9705) conforming to IEC 60529
IP54 conforming to IEC 61800-5-1
operating altitude 1000...4800 m with current derating 1 % per 100 m
<= 1000 m without derating
Range of product Altivar Process ATV600
ambient air temperature for operation 50…60 °C (with derating factor)
-15…40 °C (without derating)
electromagnetic compatibility Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
overvoltage category III
standards EN/IEC 61800-3
EN/IEC 61800-3 environment 2 category C3
EN/IEC 61800-5-1
IEC 61000-3-12
IEC 60721-3
IEC 61508
IEC 13849-1
UL 508C
relative humidity 5…95 % without condensation conforming to IEC 60068-2-3
Maximum thdi <48 % full load conforming to IEC 61000-3-12
Regulation loop Adjustable PID regulator
vibration resistance 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6
insulation resistance > 1 MOhm 500 V DC for 1 minute to earth
Recently viewed
11 984,09 €
11 984,09 € incl. VAT
Expected in 2-4 weeks