Complementary
Accuracy
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
maximum switching current
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
Product certifications
TÜV
UL
CSA
data formats
8 bits, configurable odd, even or no parity
Handle front plate colour
630 mm
Product or component type
Variable speed drive
[us] rated supply voltage
500...690 V - 15...10 %
minimum switching current
Relay output R1, R2, R3: 5 mA at 24 V DC
noise level
56 dB
marking
CE
Quantity per set
1
Analogue input number
3
Analogue input type
AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm, resolution 12 bits
AI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits
AI2 voltage analog input: - 10...10 V DC, impedance: 31.5 kOhm, resolution 12 bits
refresh time
Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
Analogue output number
2
Asynchronous motor control profile
Optimized torque mode
Constant torque standard
Variable torque standard
Discrete input logic
Positive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1)
Negative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1)
output voltage
<= power supply voltage
width (w)
331 mm
Analogue output type
Software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits
Software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits
Software-configurable current DQ-, DQ+: 30 V DC
Software-configurable current DQ-, DQ+: 100 mA
Discrete input type
DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
isolation
Between power and control terminals
switching frequency
1...4.9 kHz adjustable
2.5...4.9 kHz with derating factor
Local signalling
3 LEDs for local diagnostic
3 LEDs (dual colour) for embedded communication status
4 LEDs (dual colour) for communication module status
1 LED (red) for presence of voltage
motor slip compensation
Can be suppressed
Adjustable
Not available in permanent magnet motor law
Automatic whatever the load
Mounting mode
Wall mount
Braking to standstill
By DC injection
Discrete input number
8
Net weight
53 kg
physical interface
Ethernet
2-wire RS 485
Discrete output type
Relay outputs R1A, R1B, R1C 250 V AC 3000 mA
Relay outputs R1A, R1B, R1C 30 V DC 3000 mA
Relay outputs R2A, R2C 250 V AC 5000 mA
Relay outputs R2A, R2C 30 V DC 5000 mA
Relay outputs R3A, R3C 250 V AC 5000 mA
Relay outputs R3A, R3C 30 V DC 5000 mA
Operating position
Vertical +/- 10 degree
communication port protocol
Ethernet
Modbus serial
Modbus TCP
Motor power hp
75 hp at 500 V normal duty
60 hp at 500 V heavy duty
100 hp at 690 V normal duty
75 hp at 690 V heavy duty
connector type
RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP
RJ45 (on the remote graphic terminal) for Modbus serial
depth
297 mm
line current
82.7 A at 500 V (normal duty)
87.7 A at 690 V (normal duty)
71 A at 500 V (heavy duty)
68.5 A at 690 V (heavy duty)
power dissipation in w
Natural convection: 268 W at 500 V, switching frequency 2.5 kHz
Forced convection: 1075 W at 500 V, switching frequency 2.5 kHz
continuous output current
83 A at 2.5 kHz for normal duty
66 A at 2.5 kHz for heavy duty
maximum transient current
91.3 A during 60 s (normal duty)
99 A during 60 s (heavy duty)
Permissible temporary current boost
1.1 x In during 60 s (normal duty)
1.5 x In during 60 s (heavy duty)
Pollution degree
2
electrical connection
Control: removable screw terminals 0.5...1.5 mm²/AWG 20...AWG 16
Line side: screw terminal 35...50 mm²/AWG 2...AWG 1
Motor: screw terminal 35...50 mm²/AWG 2...AWG 1
linearity error
AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input
AO1, AO2: +/- 0.2 % for analog output
Network number of phases
3 phases
nominal switching frequency
2.5 kHz
Enclosure mounting
Wall mounted
maximum output frequency
500 kHz
Exchange mode
Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Input compatibility
DI1...DI6: discrete input level 1 PLC conforming to EN/IEC 61131-2
DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68
STOA, STOB: discrete input level 1 PLC conforming to EN/IEC 61131-2
Product destination
Asynchronous motors
Synchronous motors
Maximum input current
87.7 A
Shock resistance
15 gn for 11 ms conforming to IEC 60068-2-27
Method of access
Slave Modbus TCP
synchronous motor control profile
Permanent magnet motor
Synchronous reluctance motor
Supply frequency
50...60 Hz - 5...5 %
apparent power
104.8 kVA at 690 V (normal duty)
81.9 kVA at 690 V (heavy duty)
number of addresses
1…247 for Modbus serial
Supply
External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
Internal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection
acceleration and deceleration ramps
S, U or customized
Linear adjustable separately from 0.01...9999 s
Protection type
Thermal protection: motor
Safe torque off: motor
Motor phase break: motor
Thermal protection: drive
Safe torque off: drive
Overheating: drive
Overcurrent between output phases and earth: drive
Overload of output voltage: drive
Short-circuit protection: drive
Motor phase break: drive
Overvoltages on the DC bus: drive
Line supply overvoltage: drive
Line supply undervoltage: drive
Line supply phase loss: drive
Overspeed: drive
Break on the control circuit: drive
Option card
Slot A: communication module, Profibus DP V1
Slot A: communication module, PROFINET
Slot A: communication module, DeviceNet
Slot A: communication module, Modbus TCP/EtherNet/IP
Slot A: communication module, CANopen daisy chain RJ45
Slot A: communication module, CANopen SUB-D 9
Slot A: communication module, CANopen screw terminals
Slot A/slot B: digital and analog I/O extension module
Slot A/slot B: output relay extension module
Slot A: communication module, Ethernet IP/Modbus TCP/MD-Link
Communication module, BACnet MS/TP
Communication module, Ethernet Powerlink
relay output type
Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles
Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles
Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
Transmission rate
10, 100 Mbits
4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Type of cooling
Forced convection
frequency resolution
Display unit: 0.1 Hz
Analog input: 0.012/50 Hz
Prospective line isc
70 kA
transmission frame
RTU
Relay output number
3
Sampling duration
2 ms +/- 0.5 ms (DI1...DI4) - discrete input
5 ms +/- 1 ms (DI5, DI6) - discrete input
5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input
10 ms +/- 1 ms (AO1) - analog output
Speed drive output frequency
0.1…500 Hz
Type of polarization
No impedance
Volume of cooling air
406 m3/h