Complementary
4 quadrant operation possible
True
with safety function safe brake management (sbc/sbt)
True
maximum switching current
Relay output R1C on resistive load, cos phi = 1: 3 A at 250 V AC
Relay output R1C on resistive load, cos phi = 1: 3 A at 30 V DC
Relay output R1C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
Relay output R1C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
Relay output R2C on resistive load, cos phi = 1: 5 A at 250 V AC
Relay output R2C on resistive load, cos phi = 1: 5 A at 30 V DC
Relay output R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
Relay output R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
Product certifications
UL
CSA
TÜV
EAC
CTick
with safety function safe operating stop (sos)
False
data formats
8 bits, configurable odd, even or no parity
Handle front plate colour
270.0 mm
Product or component type
Variable speed drive
[us] rated supply voltage
380...480 V - 15...10 %
Assembly style
With heat sink
with safety function safe programmable logic
False
minimum switching current
Relay output R1B: 5 mA at 24 V DC
Relay output R2C: 5 mA at 24 V DC
noise level
52.7 dB
marking
CE
with safety function safe stop 1 (ss1)
True
Analogue input number
2
Analogue input type
AI1 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits
AI1 software-configurable temperature probe or water level sensor
AI1 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm, resolution 12 bits
AI2 software-configurable voltage: - 10...10 V DC, impedance: 31.5 kOhm, resolution 12 bits
Analogue output number
2
Asynchronous motor control profile
Constant torque standard
Variable torque standard
Optimized torque mode
output voltage
<= power supply voltage
width (w)
85.0 mm
Analogue output type
Software-configurable voltage AQ1: 0...10 V DC impedance 470 Ohm, resolution 10 bits
Software-configurable current AQ1: 0...20 mA impedance 500 Ohm, resolution 10 bits
Discrete input type
PTI programmable as pulse input: 0…30 kHz, 24 V DC (30 V)
DI1...DI5 safe torque off, 24 V DC (30 V), impedance: 3.5 kOhm
programmable
isolation
Between power and control terminals
switching frequency
2...16 kHz adjustable
14...16 kHz with derating factor
with safety function safely limited speed (sls)
True
Brake chopper integrated
True
motor slip compensation
Can be suppressed
Not available in permanent magnet motor law
Automatic whatever the load
Adjustable
Mounting mode
Cabinet mount
Braking to standstill
By DC injection
Discrete input number
5
Net weight
1.7 kg
physical interface
2-wire RS 485
Base load current at low overload
2.8 A
Discrete output type
Programmable output DQ1, DQ2 30 V DC 100 mA
base load current at high overload
2.2 A
Operating position
Vertical +/- 10 degree
communication port protocol
Modbus serial
Discrete output number
2.0
Motor power hp
1.5 hp for normal duty
1 hp for heavy duty
connector type
1 RJ45
depth
232.5 mm
line current
2.6 A at 480 V without line choke (heavy duty)
2.6 A at 380 V with external line choke (normal duty)
2.1 A at 480 V with external line choke (normal duty)
1.9 A at 380 V with external line choke (heavy duty)
1.6 A at 480 V with external line choke (heavy duty)
3.4 A at 380 V without line choke (heavy duty)
power dissipation in w
Natural convection: 28 W at 380 V, switching frequency 4 kHz (heavy duty)
Forced convection: 28 W at 380 V, switching frequency 4 kHz (heavy duty)
Natural convection: 33 W at 380 V, switching frequency 4 kHz (normal duty)
Forced convection: 33 W at 380 V, switching frequency 4 kHz (normal duty)
continuous output current
2.2 A at 4 kHz for heavy duty
2.8 A at 4 kHz for normal duty
maximum transient current
3.1 A during 60 s (normal duty)
3.3 A during 60 s (heavy duty)
3.8 A during 2 s (normal duty)
4 A during 2 s (heavy duty)
Pollution degree
2 conforming to EN/IEC 61800-5-1
electrical connection
Line side: screw terminal 1.5...4 mm²/AWG 14...AWG 12
DC bus: screw terminal 4...6 mm²/AWG 12...AWG 10
Motor: screw terminal 1.5...4 mm²/AWG 14...AWG 12
Control: screw terminal 0.2...2.5 mm²/AWG 24...AWG 12
Network number of phases
3 phases
nominal switching frequency
4 kHz
maximum output frequency
0.599 kHz
Maximum input current
3.4 A
Maximum output voltage
480 V
Method of access
Slave Modbus RTU
synchronous motor control profile
Permanent magnet motor
Reluctance motor
Supply frequency
50...60 Hz +/- 5 %
apparent power
2.2 kVA at 480 V (normal duty)
2.2 kVA at 480 V (heavy duty)
number of addresses
1…247
acceleration and deceleration ramps
S, U or customized
Linear adjustable separately from 0.01...9999 s
Nominal output current
2.2 A
Protection type
Thermal protection: motor
Safe torque off: motor
Motor phase loss: motor
Thermal protection: drive
Safe torque off: drive
Overheating: drive
Overcurrent: drive
Output overcurrent between motor phase and earth: drive
Output overcurrent between motor phases: drive
Short-circuit between motor phase and earth: drive
Short-circuit between motor phases: drive
Motor phase loss: drive
DC Bus overvoltage: drive
Line supply overvoltage: drive
Line supply undervoltage: drive
Input supply loss: drive
Exceeding limit speed: drive
Break on the control circuit: drive
Option card
Communication module, Profibus DP V1
Communication module, PROFINET
Communication module, DeviceNet
Communication module, CANopen
Communication module, EtherCAT
relay output type
Relay outputs R1A
Relay outputs R1C electrical durability 100000 cycles
Relay outputs R2A
Relay outputs R2C electrical durability 100000 cycles
Transmission rate
4.8 kbit/s
9.6 kbit/s
19.2 kbit/s
38.4 kbit/s
Number of preset speeds
16 preset speeds
Type of cooling
Forced convection
Prospective line isc
5 kA
transmission frame
RTU
Relay output number
2
Type of polarization
No impedance
Volume of cooling air
18.0 m3/h
With safety function safe direction (sdi)
False
With safety function safe position (sp)
False
With safety function safe speed monitor (ssm)
False
With safety function safe torque off (sto)
True
With safety function safely limited position (slp)
False
With sft fct safe stop 2 (ss2)
False
Environment
Ambient air temp for storage/transportation
-40…70 °C
Environmental class (during operation)
Class 3C3 according to IEC 60721-3-3
Class 3S3 according to IEC 60721-3-3
ip degree of protection
IP20
operating altitude
<= 3000 m with current derating above 1000m
Range of product
Altivar Machine ATV340
ambient air temperature for operation
-15…50 °C without derating (vertical position)
50…60 °C with derating factor (vertical position)
electromagnetic compatibility
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Maximum acceleration under shock impact (during operation)
70 m/s² at 22 ms
overvoltage category
Class III
standards
EN/IEC 61800-3
EN/IEC 61800-5-1
IEC 60721-3
IEC 61508
IEC 13849-1
UL 618000-5-1
UL 508C
Maximum acceleration under vibrational stress (during operation)
5 m/s² at 9...200 Hz
Permitted relative humidity (during operation)
Class 3K5 according to EN 60721-3
Maximum deflection under vibratory load (during operation)
1.5 mm at 2...9 Hz
Regulation loop
Adjustable PID regulator