Complementary
specific application
HVAC
Accuracy
+/- 0.6 % (VIA) for a temperature variation 60 °C
+/- 0.6 % (VIB) for a temperature variation 60 °C
+/- 1 % (FM) for a temperature variation 60 °C
maximum switching current
5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)
5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)
2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)
2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)
Product certifications
C-Tick
UL
NOM 117
CSA
response time
FM 2 ms, tolerance +/- 0.5 ms for analog output(s)
FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
data formats
8 bits, 1 stop, odd even or no configurable parity
Handle front plate colour
420 mm
Product or component type
Variable speed drive
tightening torque
0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)
24 N.m, 212 lb.in (L1/R, L2/S, L3/T)
[us] rated supply voltage
380...480 V - 15...10 %
Assembly style
With heat sink
minimum switching current
3 mA at 24 V DC for configurable relay logic
noise level
59.9 dB conforming to 86/188/EEC
marking
CE
Analogue input number
2
Analogue input type
VIA switch-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
VIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
VIB configurable PTC probe: 0...6 probes, impedance: 1500 Ohm
VIA switch-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 10 bits
Analogue output number
1
Asynchronous motor control profile
Voltage/frequency ratio, 2 points
Voltage/frequency ratio - Energy Saving, quadratic U/f
Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)
Flux vector control without sensor, standard
Voltage/frequency ratio, 5 points
Discrete input logic
Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1)
Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1)
output voltage
<= power supply voltage
width (w)
240 mm
Analogue output type
FM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bits
FM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bits
Discrete input type
F programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
isolation
Electrical between power and control
network frequency
47.5...63 Hz
supply voltage limits
323…528 V
switching frequency
6...16 kHz adjustable
8...16 kHz with derating factor
Local signalling
1 LED (red) for DC bus energized
motor slip compensation
Adjustable
Not available in voltage/frequency ratio motor control
Automatic whatever the load
Braking to standstill
By DC injection
Net weight
26.4 kg
physical interface
2-wire RS 485
Discrete output type
Configurable relay logic: (FLA, FLC) NO - 100000 cycles
Configurable relay logic: (FLB, FLC) NC - 100000 cycles
Configurable relay logic: (RY, RC) NO - 100000 cycles
Communication service
Write single register (06)
Read device identification (43)
Read holding registers (03) 2 words maximum
Write multiple registers (16) 2 words maximum
Time out setting from 0.1 to 100 s
Monitoring inhibitable
Operating position
Vertical +/- 10 degree
communication port protocol
Modbus
LonWorks
APOGEE FLN
BACnet
METASYS N2
Discrete output number
2
functionality
Mid
Motor power hp
30 hp
connector type
1 RJ45
1 open style
depth
214 mm
line current
33.1 A at 480 V
41.6 A at 380 V
power dissipation in w
626 W
continuous output current
43.5 A at 380 V
43.5 A at 460 V
Motor power range ac-3
15…25 kW at 380…440 V 3 phases
15…25 kW at 480…500 V 3 phases
maximum transient current
47.9 A for 60 s
Pollution degree
3 conforming to IEC 61800-5-1
electrical connection
VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / AWG 14
L1/R, L2/S, L3/T: terminal 50 mm² / AWG 1/0
linearity error
VIA: +/- 0.15 % of maximum value for input
VIB: +/- 0.15 % of maximum value for input
FM: +/- 0.2 % for output
Network number of phases
3 phases
nominal switching frequency
8 kHz
dielectric strength
3535 V DC between earth and power terminals
5092 V DC between control and power terminals
motor starter type
Variable speed drive
Product destination
Asynchronous motors
speed range
1…10
Shock resistance
15 gn for 11 ms conforming to IEC 60068-2-27
Supply frequency
50...60 Hz - 5...5 %
torque accuracy
+/- 15 %
apparent power
33.2 kVA at 380 V
number of addresses
1…247
Supply
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type: overload and short-circuit protection
Internal supply: 24 V DC (21…27 V), <200 A, protection type: overload and short-circuit protection
variable speed drive application selection
Building - HVAC compressor for scroll
Building - HVAC fan
Building - HVAC pump
acceleration and deceleration ramps
Automatic based on the load
Linear adjustable separately from 0.01 to 3200 s
transient overtorque
120 % of nominal motor torque +/- 10 % for 60 s
Protection type
Overheating protection: drive
Thermal power stage: drive
Short-circuit between motor phases: drive
Input phase breaks: drive
Overcurrent between output phases and earth: drive
Overvoltages on the DC bus: drive
Break on the control circuit: drive
Against exceeding limit speed: drive
Line supply overvoltage and undervoltage: drive
Line supply undervoltage: drive
Against input phase loss: drive
Thermal protection: motor
Motor phase break: motor
With PTC probes: motor
Option card
Communication card for LonWorks
Transmission rate
9600 bps or 19200 bps
frequency resolution
Display unit: 0.1 Hz
Analog input: 0.024/50 Hz
Prospective line isc
22 kA
transmission frame
RTU
Sampling duration
2 ms +/- 0.5 ms F discrete
2 ms +/- 0.5 ms R discrete
2 ms +/- 0.5 ms RES discrete
3.5 ms +/- 0.5 ms VIA analog
22 ms +/- 0.5 ms VIB analog
Speed drive output frequency
0.5…200 Hz
Type of polarization
No impedance
Type of cable
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC
With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC