Complementary
4 quadrant operation possible
False
with safety function safe brake management (sbc/sbt)
False
Product certifications
NOM
CSA
C-Tick
UL
GOST
RCM
KC
with safety function safe operating stop (sos)
False
data formats
8 bits, configurable odd, even or no parity
Handle front plate colour
143 mm
Product or component type
Variable speed drive
tightening torque
0.8 N.m
[us] rated supply voltage
200...240 V - 15...10 %
Assembly style
On base plate
with safety function safe programmable logic
False
noise level
0 dB
marking
CE
Quantity per set
Set of 1
with safety function safe stop 1 (ss1)
False
Analogue input number
1
Analogue output number
1
Asynchronous motor control profile
Voltage/frequency ratio (V/f)
Sensorless flux vector control
Quadratic voltage/frequency ratio
width (w)
72 mm
network frequency
50...60 Hz
switching frequency
2...16 kHz adjustable
4...16 kHz with derating factor
with safety function safely limited speed (sls)
False
Brake chopper integrated
False
motor slip compensation
Preset in factory
Adjustable
Mounting mode
Cabinet mount
Braking to standstill
By DC injection
Discrete input number
4
Net weight
0.7 kg
physical interface
2-wire RS 485
time constant
20 ms +/- 1 ms for reference change
base load current at high overload
1.4 A
Communication service
Read holding registers (03) 29 words
Write single register (06) 29 words
Write multiple registers (16) 27 words
Read/write multiple registers (23) 4/4 words
Read device identification (43)
Operating position
Vertical +/- 10 degree
communication port protocol
Modbus
Discrete output number
2
Motor power hp
0.25 hp
connector type
1 RJ45
depth
102.2 mm
line current
3.4 A at 100 V (heavy duty)
2.8 A at 120 V (heavy duty)
power dissipation in w
Natural: 18.0 W
continuous output current
1.4 A at 4 kHz
maximum transient current
2.1 A during 60 s (heavy duty)
2.3 A during 2 s (heavy duty)
Pollution degree
2
linearity error
+/- 0.3 % of maximum value for analogue input
nominal switching frequency
4 kHz
maximum output frequency
4 kHz
Insulation
Electrical between power and control
Maximum input current
2.8 A
speed range
1…20
Maximum output voltage
240 V
Shock resistance
15 gn conforming to EN/IEC 60068-2-27 for 11 ms
Method of access
Server Modbus serial
Supply frequency
50/60 Hz +/- 5 %
apparent power
0.7 kVA at 240 V (heavy duty)
number of addresses
1…247
acceleration and deceleration ramps
U
Linear from 0 to 999.9 s
S
transient overtorque
150…170 % of nominal motor torque depending on drive rating and type of motor
Nominal output current
1.4 A
Protection type
Line supply overvoltage
Line supply undervoltage
Overcurrent between output phases and earth
Overheating protection
Short-circuit between motor phases
Against input phase loss in three-phase
Thermal motor protection via the drive by continuous calculation of I²t
Transmission rate
9.6 kbit/s
19.2 kbit/s
38.4 kbit/s
frequency resolution
Analog input: converter A/D, 10 bits
Display unit: 0.1 Hz
Prospective line isc
1 kA
transmission frame
RTU
Relative symmetric network frequency tolerance
5 %
Relay output number
1
Sampling duration
20 ms, tolerance +/- 1 ms for logic input
10 ms for analogue input
Speed drive output frequency
0.5…400 Hz
Type of polarization
No impedance
With safety function safe direction (sdi)
False
With safety function safe position (sp)
False
With safety function safe speed monitor (ssm)
False
With safety function safe torque off (sto)
False
With safety function safely limited position (slp)
False
With sft fct safe stop 2 (ss2)
False
Environment
Ambient air temp for storage/transportation
-25…70 °C
Environmental class (during operation)
Class 3C3 according to IEC 60721-3-3
Class 3S2 according to IEC 60721-3-3
ip degree of protection
IP20
operating altitude
> 1000...2000 m with current derating 1 % per 100 m
<= 1000 m without derating
Range of product
Altivar 12
ambient air temperature for operation
-10…40 °C without derating
40…60 °C with current derating 2.2 % per °C
electromagnetic compatibility
Electrical fast transient/burst immunity test level 4 conforming to EN/IEC 61000-4-4
Electrostatic discharge immunity test level 3 conforming to EN/IEC 61000-4-2
Immunity to conducted disturbances level 3 conforming to EN/IEC 61000-4-6
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to EN/IEC 61000-4-3
Surge immunity test level 3 conforming to EN/IEC 61000-4-5
Voltage dips and interruptions immunity test conforming to EN/IEC 61000-4-11
Maximum acceleration under shock impact (during operation)
150 m/s² at 11 ms
overvoltage category
Class III
standards
UL 508C
UL 618000-5-1
EN/IEC 61800-5-1
EN/IEC 61800-3
relative humidity
5…95 % without condensation conforming to IEC 60068-2-3
5…95 % without dripping water conforming to IEC 60068-2-3
Maximum acceleration under vibrational stress (during operation)
10 m/s² at 13...200 Hz
electromagnetic emission
Radiated emissions environment 1 category C2 conforming to EN/IEC 61800-3 2...16 kHz shielded motor cable
Conducted emissions with integrated EMC filter environment 1 category C1 conforming to EN/IEC 61800-3 2, 4, 8, 12 and 16 kHz shielded motor cable <5 m
Conducted emissions with integrated EMC filter environment 1 category C2 conforming to EN/IEC 61800-3 2...12 kHz shielded motor cable <5 m
Conducted emissions with integrated EMC filter environment 1 category C2 conforming to EN/IEC 61800-3 2, 4 and 16 kHz shielded motor cable <10 m
Conducted emissions with additional EMC filter environment 1 category C1 conforming to EN/IEC 61800-3 4...12 kHz shielded motor cable <20 m
Conducted emissions with additional EMC filter environment 1 category C2 conforming to EN/IEC 61800-3 4...12 kHz shielded motor cable <50 m
Conducted emissions with additional EMC filter environment 2 category C3 conforming to EN/IEC 61800-3 4...12 kHz shielded motor cable <50 m
Maximum deflection under vibratory load (during operation)
1.5 mm at 2...13 Hz
Regulation loop
Adjustable PID regulator
vibration resistance
1 gn (f = 13…200 Hz) conforming to EN/IEC 60068-2-6
1.5 mm peak to peak (f = 3…13 Hz) - drive unmounted on symmetrical DIN rail - conforming to EN/IEC 60068-2-6