All categories
Compare Cart

ATS48M12Y - Soft starter for asynchronous motor, ATS48, 1170 A, 208..690 V, 250..900 KW - Schneider Electric

Expected in 2-4 weeks
ATS48M12Y - Soft starter for asynchronous motor, ATS48, 1170 A, 208..690 V, 250..900 KW - Schneider Electric - Soft starter for asynchronous motor, ATS48, 1170 A, 208..690 V, 250..900 KW - Schneider Electric - 0
ATS48M12Y - Soft starter for asynchronous motor, ATS48, 1170 A, 208..690 V, 250..900 KW - Schneider Electric
14 220,82 € excl. VAT
17 349,40 € incl. VAT
Text About:
Soft starter for asynchronous motor, ATS48, 1170 A, 208..690 V, 250..900 KW - Schneider Electric
17 349,40 €
SPECIFICATIONS
Main
Device short name ATS48
product specific application Heavy duty industry and pumps
Ue power supply voltage 208...690 V - 15...10 %
motor power kW 250 kW at 230 V for severe applications
355 kW at 230 V for standard applications
500 kW at 400 V for severe applications
630 kW at 400 V for standard applications
630 kW at 440 V for severe applications
630 kW at 500 V for severe applications
630 kW at 525 V for severe applications
710 kW at 440 V for standard applications
800 kW at 500 V for standard applications
800 kW at 525 V for standard applications
900 kW at 660 V for severe applications
900 kW at 690 V for severe applications
Complementary
Product certifications GOST
CSA
C-Tick
UL
TCF
NOM 117
DNV
CCC
SEPRO
Handle front plate colour 890 mm
Product or component type Soft starter
Communication data link Serial
minimum switching current 10 mA at 6 V DC for relay outputs
marking CE
Discrete input logic Positive logic Stop, Run, LI3, LI4 at State 0: < 5 V and <= 2 mA at State 1: > 11 V, >= 5 mA
width (w) 770 mm
Analogue output type Current output AO: 0-20 mA or 4-20 mA, impedance <500 Ohm
Discrete input type PTC, 750 Ohm at 25 °C
(Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm
function available External bypass (optional)
Discrete input number 5
Net weight 115 kg
physical interface RS485 multidrop
Discrete output type (LO1) logic output 0 V common configurable
(LO2) logic output 0 V common configurable
(R1) relay outputs fault relay NO
(R2) relay outputs end of starting relay NO
(R3) relay outputs motor powered NO
Operating position Vertical +/- 10 degree
communication port protocol Modbus
Discrete output number 2
Motor power hp 1000 hp at 460 V for standard applications
1000 hp at 575 V for severe applications
1200 hp at 575 V for standard applications
350 hp at 208 V for severe applications
350 hp at 230 V for severe applications
400 hp at 208 V for standard applications
450 hp at 230 V for standard applications
800 hp at 460 V for severe applications
connector type 1 RJ45
depth 315 mm
device connection In the motor supply line
Product destination Asynchronous motors
Utilisation category AC-53A
Protection type Phase failure: line
Thermal protection: motor
Thermal protection: starter
Transmission rate 4800, 9600 or 19200 bps
Power supply frequency 50...60 Hz - 5...5 %
Environment
Ambient air temp for storage/transportation -25…70 °C
operating altitude <= 1000 m without derating
> 1000...2000 m with current derating of 2.2 % per additional 100 m
Range of product Altistart 48
ambient air temperature for operation 40…60 °C (with current derating of 2 % per °C)
-10…40 °C (without derating)
electromagnetic compatibility Conducted and radiated emissions level A conforming to IEC 60947-4-2
Damped oscillating waves level 3 conforming to IEC 61000-4-12
Electrostatic discharge level 3 conforming to IEC 61000-4-2
Immunity to electrical transients level 4 conforming to IEC 61000-4-4
Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
Voltage/current impulse level 3 conforming to IEC 61000-4-5
standards EN/IEC 60947-4-2
relative humidity 0…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
Recently viewed
14 220,82 € excl. VAT
17 349,40 € incl. VAT
Expected in 2-4 weeks