Main
Device short name
ATS48
product specific application
Heavy duty industry and pumps
Ue power supply voltage
230...415 V - 15...10 %
motor power kW
7.5 kW at 230 V connection in the motor supply line for severe applications
9 kW at 230 V connection in the motor supply line for standard applications
15 kW at 230 V connection to the motor delta terminals for severe applications
15 kW at 400 V connection in the motor supply line for severe applications
18.5 kW at 230 V connection to the motor delta terminals for standard applications
18.5 kW at 400 V connection in the motor supply line for standard applications
22 kW at 400 V connection to the motor delta terminals for severe applications
30 kW at 400 V connection to the motor delta terminals for standard applications
Complementary
Product certifications
UL
C-Tick
TCF
DNV
NOM 117
CSA
SEPRO
CCC
GOST
Handle front plate colour
275 mm
Product or component type
Soft starter
Communication data link
Serial
minimum switching current
10 mA at 6 V DC for relay outputs
marking
CE
Discrete input logic
Positive logic Stop, Run, LI3, LI4 at State 0: < 5 V and <= 2 mA at State 1: > 11 V, >= 5 mA
width (w)
160 mm
Analogue output type
Current output AO: 0-20 mA or 4-20 mA, impedance <500 Ohm
Discrete input type
PTC, 750 Ohm at 25 °C
(Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm
function available
External bypass (optional)
Discrete input number
5
Net weight
4.9 kg
physical interface
RS485 multidrop
Discrete output type
(LO1) logic output 0 V common configurable
(LO2) logic output 0 V common configurable
(R1) relay outputs fault relay NO
(R2) relay outputs end of starting relay NO
(R3) relay outputs motor powered NO
Operating position
Vertical +/- 10 degree
communication port protocol
Modbus
Discrete output number
2
connector type
1 RJ45
depth
190 mm
device connection
To the motor delta terminals
In the motor supply line
Product destination
Asynchronous motors
Utilisation category
AC-53A
Protection type
Phase failure: line
Thermal protection: motor
Thermal protection: starter
Transmission rate
4800, 9600 or 19200 bps
Power supply frequency
50...60 Hz - 5...5 %
Environment
Ambient air temp for storage/transportation
-25…70 °C
operating altitude
<= 1000 m without derating
> 1000...2000 m with current derating of 2.2 % per additional 100 m
Range of product
Altistart 48
ambient air temperature for operation
40…60 °C (with current derating of 2 % per °C)
-10…40 °C (without derating)
electromagnetic compatibility
Conducted and radiated emissions level A conforming to IEC 60947-4-2
Conducted and radiated emissions level B conforming to IEC 60947-4-2
Damped oscillating waves level 3 conforming to IEC 61000-4-12
Electrostatic discharge level 3 conforming to IEC 61000-4-2
Immunity to electrical transients level 4 conforming to IEC 61000-4-4
Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
Voltage/current impulse level 3 conforming to IEC 61000-4-5
standards
EN/IEC 60947-4-2
relative humidity
0…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3