Complementary
control circuit consumption
20 W
maximum switching current
5 A 250 V AC resistive 1 relay outputs
5 A 30 V DC resistive 1 relay outputs
2 A 250 V AC inductive 0.4 20 ms relay outputs
2 A 30 V DC inductive 7 ms relay outputs
Product certifications
CCC
C-Tick
UL
GOST
CSA
Handle front plate colour
265 mm
Product or component type
Soft starter
[us] rated supply voltage
230...440 V - 15...10 %
Assembly style
With heat sink
Communication data link
Serial
minimum switching current
100 mA at 12 V DC (relay outputs)
noise level
45 dB
output current
0.4...1 Icl adjustable
marking
CE
ptc probe input
750 Ohm
Discrete input logic
Positive logic LI1, LI2, LI3 at State 0: < 5 V and <= 2 mA at State 1: > 11 V, >= 5 mA
width (w)
130 mm
Discrete input type
(LI1, LI2, LI3) logic, 5 mA 4.3 kOhm
function available
Internal bypass
network frequency
45...66 Hz
supply voltage limits
195…484 V
Discrete input voltage
24 V <= 30 V
Discrete input number
3
Net weight
7 kg
physical interface
RS485 multidrop
Discrete output type
Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
Operating position
Vertical +/- 10 degree
communication port protocol
Modbus
Discrete output number
2
connector type
1 RJ45
depth
169 mm
power dissipation in w
48 W for standard applications
Motor power range ac-3
7…11 kW at 200…240 V 3 phases
15…25 kW at 380…440 V 3 phases
Pollution degree
Level 2 conforming to IEC 60664-1
Installed device
31
Network number of phases
3 phases
device connection
To the motor delta terminals
In the motor supply line
motor starter type
Soft starter
Product destination
Asynchronous motors
Shock resistance
15 gn for 11 ms conforming to EN/IEC 60068-2-27
Supply frequency
50...60 Hz - 10...10 %
Type of start
Start with torque control (current limited to 3.5 In)
Utilisation category
AC-53A
Protection type
Phase failure: line
Thermal protection: motor
Thermal protection: starter
Transmission rate
4800, 9600 or 19200 bps
Type of cooling
Forced convection
Environment
Ambient air temp for storage/transportation
-25…70 °C
ip degree of protection
IP20
operating altitude
<= 1000 m without derating
> 1000...< 2000 m with current derating of 2.2 % per additional 100 m
Range of product
Altistart 22
ambient air temperature for operation
-10…40 °C (without derating)
40…60 °C (with current derating 2.2 % per °C)
electromagnetic compatibility
Conducted and radiated emissions level A conforming to IEC 60947-4-2
Damped oscillating waves level 3 conforming to IEC 61000-4-12
Electrostatic discharge level 3 conforming to IEC 61000-4-2
Immunity to electrical transients level 4 conforming to IEC 61000-4-4
Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
Voltage/current impulse level 3 conforming to IEC 61000-4-5
standards
EN/IEC 60947-4-2
relative humidity
0…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
vibration resistance
1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-6
1.5 mm (f= 2…13 Hz) conforming to EN/IEC 60068-2-6