Complementary
compatibility code
ATS01N2
maximum switching current
Relay outputs: 2 A at 250 V AC cos phi = 0.5 and L/R = 20 ms inductive load
Relay outputs: 2 A at 30 V DC cos phi = 0.5 and L/R = 20 ms inductive load
Product certifications
UL
B44.1-96/ASME A17.5 for starter wired to the motor delta terminal
CSA
GOST
C-Tick
CCC
starting torque
30...80 % of starting torque of motor connected directly on the line supply
Handle front plate colour
124 mm
Product or component type
Soft starter
tightening torque
1.9…2.5 N.m
0.5 N.m
[us] rated supply voltage
380...415 V - 10...10 %
Assembly style
With heat sink
Current consumption
30 A at nominal load
minimum switching current
10 mA at 6 V DC for relay outputs
marking
CE
Discrete output current
2 A DC-13
3 A AC-15
Discrete input logic
Positive LI1, LI2, BOOST at State 0: < 5 V and <= 0.2 mA at State 1: > 13 V, >= 0.5 mA
output voltage
<= power supply voltage
width (w)
45 mm
Discrete input type
Logic (LI1, LI2, BOOST) stop, run and boost on start-up functions <= 8 mA 27 kOhm
function available
Integrated bypass
network frequency
47.5...63 Hz
supply voltage limits
342…456 V
Discrete input voltage
24...40 V
Net weight
0.42 kg
Discrete output type
Open collector logic LO1 end of starting signal
Relay outputs R1A, R1C NO
Discrete output voltage
24 V (voltage limits: 6...30 V) open collector logic
Operating position
Vertical +/- 10 degree
Display type
1 LED (green) for starter powered up
1 LED (yellow) for nominal voltage reached
depth
131 mm
power dissipation in w
4 W at full load and at end of starting
64 W in transient state
Motor power range ac-3
1.1…2 kW at 380…440 V 3 phases
2.2…3 kW at 380…440 V 3 phases
Pollution degree
2 conforming to EN/IEC 60947-4-2
electrical connection
4 mm screw clamp terminal - rigid 1 1...10 mm² AWG 8 power circuit
Screw connector - rigid 1 0.5...2.5 mm² AWG 14 control circuit
4 mm screw clamp terminal - rigid 2 1...6 mm² AWG 10 power circuit
Screw connector - rigid 2 0.5...1 mm² AWG 17 control circuit
Screw connector - flexible with cable end 1 0.5...1.5 mm² AWG 16 control circuit
4 mm screw clamp terminal - flexible without cable end 1 1.5...10 mm² AWG 8 power circuit
Screw connector - flexible without cable end 1 0.5...2.5 mm² AWG 14 control circuit
4 mm screw clamp terminal - flexible with cable end 2 1...6 mm² AWG 10 power circuit
4 mm screw clamp terminal - flexible without cable end 2 1.5...6 mm² AWG 10 power circuit
Screw connector - flexible without cable end 2 0.5...1.5 mm² AWG 16 control circuit
deceleration time symbol
Adjustable from 1 to 10 s
Network number of phases
3 phases
motor starter type
Soft starter
Product destination
Asynchronous motors
Shock resistance
15 gn for 11 ms conforming to EN/IEC 60068-2-27
Starting time
1 s / 100
5 s / 20
10 s / 10
Adjustable from 1 to 10 s
Supply frequency
50...60 Hz - 5...5 %
Type of start
Start with voltage ramp
Utilisation category
AC-53B conforming to EN/IEC 60947-4-2
Environment
Ambient air temp for storage/transportation
-25…70 °C conforming to EN/IEC 60947-4-2
ip degree of protection
IP20
operating altitude
<= 1000 m without derating
> 1000 m with current derating of 2.2 % per additional 100 m
Range of product
Altistart 01
ambient air temperature for operation
-10…40 °C (without derating)
40…50 °C (with current derating of 2 % per °C)
electromagnetic compatibility
Conducted and radiated emissions level B conforming to CISPR 11
Conducted and radiated emissions level B conforming to IEC 60947-4-2
Damped oscillating waves level 3 conforming to IEC 61000-4-12
Electrostatic discharge level 3 conforming to IEC 61000-4-2
EMC immunity conforming to EN 50082-1
EMC immunity conforming to EN 50082-2
Harmonics conforming to IEC 1000-3-2
Harmonics conforming to IEC 1000-3-4
Immunity to conducted interference caused by radio-electrical fields level 3 conforming to IEC 61000-4-6
Immunity to electrical transients level 4 conforming to IEC 61000-4-4
Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
Micro-cuts and voltage fluctuation conforming to IEC 61000-4-11
Voltage/current impulse level 3 conforming to IEC 61000-4-5
standards
EN/IEC 60947-4-2
relative humidity
5…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
vibration resistance
1 gn (f= 13…150 Hz) conforming to EN/IEC 60068-2-6
1.5 mm peak to peak (f= 3…13 Hz) conforming to EN/IEC 60068-2-6