All categories
Compare Cart

ATS01N106FT - Soft starter for asynchronous motor ATS01 6 A 110..480V 0.75..3 KW - Schneider Electric

Expected in 2-4 weeks
ATS01N106FT - Soft starter for asynchronous motor ATS01 6 A 110..480V 0.75..3 KW - Schneider Electric - Soft starter for asynchronous motor ATS01 6 A 110..480V 0.75..3 KW - Schneider Electric - 0
ATS01N106FT - Soft starter for asynchronous motor ATS01 6 A 110..480V 0.75..3 KW - Schneider Electric
102,65 €
102,65 € incl. VAT
Text About:
Soft starter for asynchronous motor ATS01 6 A 110..480V 0.75..3 KW - Schneider Electric
102,65 €
SPECIFICATIONS
Main
Device short name ATS01
Icl starter rating 6 A
product specific application Simple machine
[uc] control circuit voltage 110 V AC +/- 10 % at 30 mA
24 V AC/DC +/- 10 % at 25 mA
240 V AC +/- 10 % at 65 mA
motor power kW 3 kW, 3 phases at 400 V
0.75 kW, 3 phases at 230 V
1.1 kW, 3 phases at 230 V
2.2 kW, 3 phases at 400 V
0.75 kW, 1 phase at 230 V
Complementary
compatibility code ATS01N1
Product certifications C-Tick
CCC
CSA
B44.1-96/ASME A17.5 for starter wired to the motor delta terminal
UL
GOST
starting torque 30...80 % of starting torque of motor connected directly on the line supply
Handle front plate colour 100 mm
Product or component type Soft starter
tightening torque 0.8 N.m
[us] rated supply voltage 110...480 V - 10...10 %
Assembly style With heat sink
Current consumption 30 A at nominal load
marking CE
Discrete output current 2 A DC-13
3 A AC-15
output voltage <= power supply voltage
width (w) 23 mm
function available Integrated bypass
network frequency 47.5...63 Hz
supply voltage limits 99…528 V
Net weight 0.16 kg
Operating position Vertical +/- 10 degree
Motor power hp 1 hp, 3 phases at 230 V
2 hp, 3 phases at 460 V
3 hp, 3 phases at 460 V
0.5 hp, 3 phases at 210 V
1.5 hp, 3 phases at 230 V
depth 100 mm
power dissipation in w 1 W at full load and at end of starting
31 W in transient state
Motor power range ac-3 0.55…1 kW at 200…240 V 3 phases
1.1…2 kW at 380…440 V 3 phases
0.55…1 kW at 200…240 V 1 phase
1.1…2 kW at 200…240 V 3 phases
2.2…3 kW at 380…440 V 3 phases
Pollution degree 2 conforming to EN/IEC 60947-4-2
electrical connection Cage type connector - rigid 1 2.5 mm² AWG 14 control circuit
Cage type connector - rigid 1 2.5 mm² AWG 14 power circuit
Cage type connector - rigid 2 1 mm² AWG 17 control circuit
Cage type connector - rigid 2 1 mm² AWG 17 power circuit
Cage type connector - flexible with cable end 1 2.5 mm² AWG 14 control circuit
Cage type connector - flexible with cable end 1 2.5 mm² AWG 14 power circuit
Cage type connector - flexible without cable end 1 2.5 mm² AWG 14 control circuit
Cage type connector - flexible without cable end 1 2.5 mm² AWG 14 power circuit
Cage type connector - flexible with cable end 2 0.75 mm² AWG 18 control circuit
Cage type connector - flexible with cable end 2 0.75 mm² AWG 18 power circuit
Cage type connector - flexible without cable end 2 1 mm² AWG 17 control circuit
Cage type connector - flexible without cable end 2 1 mm² AWG 17 power circuit
Network number of phases 1 phase
motor starter type Soft starter
Product destination Asynchronous motors
Shock resistance 15 gn for 11 ms conforming to EN/IEC 60068-2-27
Starting time 1 s / 100
5 s / 20
Adjustable from 1 to 5 s
Supply frequency 50...60 Hz - 5...5 %
Type of start Start with voltage ramp
Utilisation category AC-53B conforming to EN/IEC 60947-4-2
Environment
Ambient air temp for storage/transportation -25…70 °C conforming to EN/IEC 60947-4-2
ip degree of protection IP20
operating altitude <= 1000 m without derating
> 1000 m with current derating of 2.2 % per additional 100 m
Range of product Altistart 01
ambient air temperature for operation -10…40 °C (without derating)
40…50 °C (with current derating of 2 % per °C)
electromagnetic compatibility Conducted and radiated emissions level B conforming to CISPR 11
Conducted and radiated emissions level B conforming to IEC 60947-4-2
Damped oscillating waves level 3 conforming to IEC 61000-4-12
Electrostatic discharge level 3 conforming to IEC 61000-4-2
EMC immunity conforming to EN 50082-1
EMC immunity conforming to EN 50082-2
Harmonics conforming to IEC 1000-3-2
Harmonics conforming to IEC 1000-3-4
Immunity to conducted interference caused by radio-electrical fields level 3 conforming to IEC 61000-4-6
Immunity to electrical transients level 4 conforming to IEC 61000-4-4
Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
Micro-cuts and voltage fluctuation conforming to IEC 61000-4-11
Voltage/current impulse level 3 conforming to IEC 61000-4-5
standards EN/IEC 60947-4-2
relative humidity 5…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
vibration resistance 1 gn (f= 13…150 Hz) conforming to EN/IEC 60068-2-6
1.5 mm peak to peak (f= 3…13 Hz) conforming to EN/IEC 60068-2-6
Recently viewed
102,65 €
102,65 € incl. VAT
Expected in 2-4 weeks