All categories
Compare Cart

ABT7PDU250G - Voltage transformer 230..400 V 2 x 115 V 2.5 KVA - Schneider Electric

Expected in 2-4 weeks
ABT7PDU250G - Voltage transformer 230..400 V 2 x 115 V 2.5 KVA - Schneider Electric - Voltage transformer 230..400 V 2 x 115 V 2.5 KVA - Schneider Electric - 0
ABT7PDU250G - Voltage transformer 230..400 V 2 x 115 V 2.5 KVA - Schneider Electric
1 188,56 € excl. VAT
1 450,04 € incl. VAT
Text About:
Voltage transformer 230..400 V 2 x 115 V 2.5 KVA - Schneider Electric
1 450,04 €
SPECIFICATIONS
Main
secondary winding Double
Complementary
electrical insulation class Class F
output coupling Grounding of secondary
Parallel
Series by internal jumper
Product certifications EAC
UR
DNV-GL
Handle front plate colour 189.0 mm
Product or component type Safety and isolation transformer
Connections - terminals For input connection: screw type terminals, connection capacity: 5 x 4 mm² AWG 11
For input ground connection: screw type terminals, connection capacity: 1 x 4 mm² AWG 11
For output connection: screw type terminals, connection capacity: 6 x 10 mm² AWG 6
Efficiency 96 %
rated power in va 2500 VA
marking CE
network frequency limits 47…63 Hz
Fixing mode By 4 screws diameter: 10 mm on vertical panel, operating position: horizontal
By 4 screws diameter: 10 mm on vertical panel, operating position: vertical
By 4 screws diameter: 10 mm on horizontal panel with derating to 90 %
output voltage 115/230 V AC
width (w) 192.0 mm
input voltage limits 360...440 V
207...253 V
Net weight 24.91 kg
Maximum voltage drop at rated load 1.7 %
depth 205.0 mm
power dissipation in w 104.2 W
input voltage tolerance +/- 15 V
No load losses 31.6 W
input voltage 230 V AC single phase, terminal(s): N-L1
400 V AC phase to phase, terminal(s): L1-L2
Output sustained overvoltage 1.5 % (no load, hot state)
dielectric strength 3200 V between input and ground
3200 V between output and ground
5100 V between input and output
output protection type Against overload, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection
Against overvoltage, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection
Against short-circuits, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection
Protective cover Without
Short-circuit voltage 0,022
Voltage variation at nominal load 0,017 at 230 V
0,0189 at 400 V
Environment
Ambient air temp for storage/transportation -40…80 °C
ip degree of protection IP20
operating altitude 3000 m
Range of product Modicon Transformer Universal
ambient air temperature for operation -20…60 °C
Environmental characteristics EMC conforming to EN 62041
Safety conforming to EN 61558-1
Safety conforming to EN 61558-2-4
overvoltage category Class I conforming to VDE 0106-1
standards UL 506
relative humidity 0…95 % during operation
Recently viewed
1 188,56 € excl. VAT
1 450,04 € incl. VAT
Expected in 2-4 weeks