Main
Nominal input voltage
100...240 V AC single phase
100...240 V AC 2 phases
140...340 V DC
Power supply output current
2.5 A
Power supply type
Regulated switch mode
service life
10 year(s)
Variant option
Optimized
Complementary
output coupling
Parallel
Product certifications
CE
CUL listed
CUL recognized
RCM
CB Scheme
EAC
KC
Handle front plate colour
123.6 mm
maximum leakage current
1 mA 240 V AC
power factor
0.55 at 115 V AC
0.45 at 230 V AC
Product or component type
Power supply
Current consumption
< 2.5 A 115 V AC
< 1.4 A 230 V AC
< 1.3 A 140 V DC
inrush current
30.0 A at 115 V
60.0 A at 230 V
Connections - terminals
Screw connection: 0.5...4 mm², (AWG 20...AWG 12) without wire end ferrule for output
Screw connection: 0.5...2.5 mm², (AWG 20...AWG 14) with wire end ferrule for output
Screw connection: 0.75...4 mm², (AWG 18...AWG 12) without wire end ferrule for input
Screw connection: 0.75...4 mm², (AWG 18...AWG 12) with wire end ferrule for input
Efficiency
85 % at 115 V AC
88 % at 230 V AC
Enclosure material
Aluminium
Electrical shock protection class
Class I
nominal network frequency
50…60 Hz
output voltage
48 V DC
width (w)
40 mm
input voltage limits
85...264 V AC (without temperature derating)
120...375 V DC (without temperature derating)
85…120 V DC (with temperature derating)
line and load regulation
< 0.5 % network 0 to 100 % load at 25 °C
< 1 % network full voltage range in line at 25 °C
Net weight
0.55 kg
holding time
> 20 ms 115 V AC
> 40 ms 230 V AC
residual ripple
< 150 mV
Mounting support
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
Double-profile DIN rail
depth
117.6 mm
Meantime between failure [mtbf]
700000 h at 25 °C, full load conforming to SR 332
power dissipation in w
23 W
Network system compatibility
TN
TT
IT
Pollution degree
2
output voltage adjustment
44...56 V
Rated power in w
120 W
dielectric strength
3000 V AC with input to output
output protection type
Against overload and short-circuits, protection technology: automatic reset
Against over temperature, protection technology: manual reset
Against overvoltage, protection technology: manual reset
input protection type
Integrated fuse (not interchangeable) 4 A
External protection (recommended) 20 A Curve C
External protection (recommended) 13 A Curve C
Shock resistance
100 m/s² for 11 ms
Startup with capacitive loads
4000 µF
Status led
1 LED (green) output voltage
Supply
SELV conforming to EN/IEC 60950-1
SELV conforming to EN/IEC 60204-1
SELV conforming to IEC 60364-4-41
Turn-on time
< 1 s
Environment
ip degree of protection
IP20
operating altitude
< 5000 m
Range of product
Modicon Power Supply
ambient air temperature for operation
-20…-10 °C with current derating of 2 % per °C mounting position A < 2000 m
-10…40 °C without derating mounting position A 115 V AC < 2000 m
-10…50 °C without derating mounting position A 230 V AC < 2000 m
40…70 °C with current derating of 1.67 % per °C mounting position A 115 V AC < 2000 m
50…70 °C with current derating of 2.5 % per °C mounting position A 230 V AC < 2000 m
Environmental characteristics
3M4 conforming to IEC 60721-3-3
standards
EN 62368-1
EN/IEC 61204-3
EN 61000-6-1
EN 61000-6-2
EN 61000-6-3
EN 61000-6-4
EN 61000-3-2
EN 61000-3-3
UL 62368-1
CSA C22.2 No 62368-1
UL 508
CSA C22.2 No 107.1
EN/IEC 62368-1
electromagnetic emission
Conducted emissions conforming to EN 61000-6-3
Radiated emissions conforming to EN 61000-6-4
vibration resistance
3 mm (f= 2…9 Hz) conforming to IEC 60068-2-6
10 m/s² (f= 9…200 Hz) conforming to IEC 60068-2-6
electromagnetic immunity
Immunity to electrostatic discharge - test level: 6 kV (contact discharge) conforming to EN/IEC 61000-4-2
Immunity to electrostatic discharge - test level: 9 kV (air discharge) conforming to EN/IEC 61000-4-2
Immunity to conducted RF disturbances - test level: 10 V/m (80 MHz...2 GHz) conforming to EN/IEC 61000-4-3
Immunity to conducted RF disturbances - test level: 5 V/m (2...2.7 GHz) conforming to EN/IEC 61000-4-3
Immunity to conducted RF disturbances - test level: 3 V/m (2.7...6 GHz) conforming to EN/IEC 61000-4-3
Immunity to fast transients - test level: 4 kV (on input-output) conforming to EN/IEC 61000-4-4
Surge immunity test - test level: 3 kV (between power supply and earth) conforming to EN/IEC 61000-4-5
Surge immunity test - test level: 1.5 kV (between phases) conforming to EN/IEC 61000-4-5
Immunity to conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to EN/IEC 61000-4-6
Immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to EN/IEC 61000-4-8
Immunity to voltage dips conforming to EN/IEC 61000-4-11
Disturbing field emission conforming to EN 55016-2-3
Limits for harmonic current emissions conforming to EN 61000-3-2
Conducted disturbance emission conforming to EN 55016-1-2
Conducted disturbance emission conforming to EN 55016-2-1