Main
Nominal input voltage
100...240 V AC single phase
Power supply output current
8.5 A
Power supply type
Regulated switch mode
Variant option
Panel mount
Complementary
output coupling
Parallel
Serial
Product certifications
CE
CULus
EAC
RCM
CB Scheme
KC
Handle front plate colour
30 mm
maximum leakage current
1 mA 240 V AC
power factor
0.55 at 115 V AC
0.45 at 230 V AC
Product or component type
Power supply
Current consumption
< 2.3 A 115 V AC
< 1.5 A 230 V AC
inrush current
45 A at 115 V
85 A at 230 V
Connections - terminals
Screw connection: 0.75...2.5 mm², (AWG 18...AWG 14) without wire end ferrule
Screw connection: 0.75...1.5 mm², (AWG 18...AWG 16) with wire end ferrule
Efficiency
88 % at 230 V AC
Enclosure material
Aluminium
Electrical shock protection class
Class I
nominal network frequency
50…60 Hz
output voltage
12 V DC
width (w)
97 mm
input voltage limits
90...264 V AC
line and load regulation
< 0.5 % network 0 to 100 % load at 25 °C
< 1 % network full voltage range in line at 25 °C
Net weight
0.3 kg
holding time
> 20 ms 115 V AC
> 40 ms 230 V AC
residual ripple
< 120 mV
Mounting support
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
Double-profile DIN rail
panel mounting
depth
129 mm
Meantime between failure [mtbf]
700000 h at 25 °C, full load conforming to SR 332
power dissipation in w
21 W
Network system compatibility
TN
TT
IT
Pollution degree
2
output voltage adjustment
10.8...13.2 V
Rated power in w
100 W
dielectric strength
3750 V AC with input to output
output protection type
Against overload and short-circuits, protection technology: automatic reset
Against over temperature, protection technology: manual reset
Against overvoltage, protection technology: manual reset
input protection type
Integrated fuse (not interchangeable) 4 A
Shock resistance
100 m/s² for 11 ms
Startup with capacitive loads
4000 µF
Status led
1 LED (green) output voltage
Supply
SELV conforming to EN/IEC 60950-1
SELV conforming to EN/IEC 60204-1
SELV conforming to IEC 60364-4-41
Turn-on time
< 500 ms
Environment
ip degree of protection
IP10
operating altitude
5000 m
Range of product
Modicon Power Supply
ambient air temperature for operation
-30…50 °C without derating mounting position A, B, F, G < 2000 m
50…70 °C with current derating of 2 % per °C mounting position A, B, F, G < 2000 m
Environmental characteristics
3M4 conforming to IEC 60721-3-3
standards
EN 62368-1
EN 61010-1
EN 61010-2-201
EN 61204-3
EN 61000-6-1
EN 61000-6-2
EN 61000-6-3
EN 61000-6-4
EN 61000-3-2
EN 61000-3-3
UL 62368-1
UL 61010-1
UL 61010-2-201
CSA C22.2 No 62368-1
CSA C22.2 No 61010-1
CSA C22.2 No 61010-2-201
EN/IEC 62368-1
electromagnetic emission
Conducted emissions conforming to EN 61000-6-3
Radiated emissions conforming to EN 61000-6-4
vibration resistance
3 mm (f= 2…9 Hz) conforming to IEC 60068-2-6
10 m/s² (f= 9…200 Hz) conforming to IEC 60068-2-6
electromagnetic immunity
Immunity to electrostatic discharge - test level: 6 kV (contact discharge) conforming to EN/IEC 61000-4-2
Immunity to electrostatic discharge - test level: 9 kV (air discharge) conforming to EN/IEC 61000-4-2
Immunity to conducted RF disturbances - test level: 10 V/m (80 MHz...2 GHz) conforming to EN/IEC 61000-4-3
Immunity to conducted RF disturbances - test level: 5 V/m (2...2.7 GHz) conforming to EN/IEC 61000-4-3
Immunity to conducted RF disturbances - test level: 3 V/m (2.7...6 GHz) conforming to EN/IEC 61000-4-3
Immunity to fast transients - test level: 4 kV (on input-output) conforming to EN/IEC 61000-4-4
Surge immunity test - test level: 3 kV (between power supply and earth) conforming to EN/IEC 61000-4-5
Surge immunity test - test level: 1.5 kV (between phases) conforming to EN/IEC 61000-4-5
Immunity to conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to EN/IEC 61000-4-6
Immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to EN/IEC 61000-4-8
Immunity to voltage dips conforming to EN/IEC 61000-4-11
Disturbing field emission conforming to EN 55016-2-3
Limits for harmonic current emissions conforming to EN 61000-3-2
Conducted disturbance emission conforming to EN 55016-1-2
Conducted disturbance emission conforming to EN 55016-2-1