Main
Nominal input voltage
100...240 V AC single phase
100...240 V AC 2 phases
Power supply output current
1 A
Power supply type
Regulated switch mode
Variant option
Modular
Complementary
output coupling
Serial
Product certifications
CE
CUL listed
CUL recognized
RCM
CB Scheme
EAC
KC
NEC: class 2
Handle front plate colour
91 mm
maximum leakage current
0.25 mA 240 V AC
power factor
0.51 at 115 V AC
0.40 at 230 V AC
Product or component type
Power supply
Current consumption
< 0.4 A 115 V AC
< 0.25 A 230 V AC
inrush current
15 A at 115 V
30 A at 230 V
Connections - terminals
Screw connection: 0.5...1.5 mm², (AWG 20...AWG 16) without wire end ferrule for input/output
Screw connection: 0.5...1 mm², (AWG 20...AWG 18) with wire end ferrule for input/output
Efficiency
80 % at 115 V AC
80 % at 230 V AC
Enclosure material
Plastic
Electrical shock protection class
Class II without PE connection
nominal network frequency
50…60 Hz
output voltage
12 V DC
width (w)
18 mm
input voltage limits
90...264 V AC
line and load regulation
< 0.5 % network in line
< 1 % network 0 to 100 % load
Net weight
0.101 kg
holding time
> 10 ms 115 V AC
> 60 ms 230 V AC
residual ripple
< 100 mV
Mounting support
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
Double-profile DIN rail
panel mounting
depth
55.6 mm
Meantime between failure [mtbf]
3000000 h at 25 °C, full load
1000000 h at 55 °C, 80 % load
power dissipation in w
3 W
Network system compatibility
TN
TT
IT
Pollution degree
2
Rated power in w
12 W
dielectric strength
3000 V AC input/output
output protection type
Against overload and short-circuits, protection technology: automatic reset
Against over temperature, protection technology: manual reset
Against overvoltage, protection technology: manual reset
input protection type
Integrated fuse (not interchangeable) 3.15 A
External protection (recommended) 20 A Curve B
External protection (recommended) 20 A Curve C
External protection (recommended) 2 A Curve B
External protection (recommended) 2 A Curve C
Shock resistance
100 m/s² for 11 ms
Startup with capacitive loads
3000 µF
Status led
1 LED (green) output voltage
Supply
SELV conforming to EN/IEC 60950-1
SELV conforming to EN/IEC 60204-1
SELV conforming to IEC 60364-4-41
Turn-on time
< 2 s
Environment
ip degree of protection
IP20
operating altitude
< 2000 m overvoltage category III
2000 m...5000 m overvoltage category II
Range of product
Modicon Power Supply
ambient air temperature for operation
-25…55 °C without current derating mounting position A < 2000 m
55…70 °C with current derating of 2.67 % per °C mounting position A < 2000 m
standards
EN 62368-1
EN/IEC 61010-1
EN 61010-2-201
EN/IEC 61204-3
EN 61000-6-1
EN 61000-6-2
EN 61000-6-3
EN 61000-6-4
EN 61000-3-2
EN 61000-3-3
UL 62368-1
UL 61010-1
UL 61010-2-201
CSA C22.2 No 62368-1
CSA C22.2 No 61010-1
CSA C22.2 No 61010-2-201
EN/IEC 62368-1
electromagnetic emission
Conducted emissions conforming to EN 61000-6-3
Radiated emissions conforming to EN 61000-6-4
vibration resistance
3 mm (f= 2…9 Hz) conforming to IEC 60721-3-3
10 m/s² (f= 9…200 Hz) conforming to IEC 60721-3-3
electromagnetic immunity
Immunity to electrostatic discharge - test level: 6 kV (contact discharge) conforming to EN/IEC 61000-4-2
Immunity to electrostatic discharge - test level: 9 kV (air discharge) conforming to EN/IEC 61000-4-2
Electromagnetic field immunity test - test level: 10 V/m (80 MHz...2 GHz) conforming to EN/IEC 61000-4-3
Electromagnetic field immunity test - test level: 5 V/m (2...2.7 GHz) conforming to EN/IEC 61000-4-3
Electromagnetic field immunity test - test level: 3 V/m (2.7...6 GHz) conforming to EN/IEC 61000-4-3
Immunity to fast transients - test level: 4 kV (on input-output) conforming to EN/IEC 61000-4-4
Surge immunity test - test level: 3 kV (between power supply and earth) conforming to EN/IEC 61000-4-5
Surge immunity test - test level: 1.5 kV (between phases) conforming to EN/IEC 61000-4-5
Immunity to conducted disturbances - test level: 10 Vrms (0.15...80 MHz) conforming to EN/IEC 61000-4-6
Immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to EN/IEC 61000-4-8
Immunity to voltage dips - test level: 100 % (1 cycle) conforming to EN/IEC 61000-4-11
Immunity to voltage dips - test level: 60 % (10 cycles) conforming to EN/IEC 61000-4-11
Immunity to voltage dips - test level: 30 % (25 cycles) conforming to EN/IEC 61000-4-11
Disturbing field emission conforming to EN 55016-2-3
Limits for harmonic current emissions conforming to EN 61000-3-2
Conducted disturbance emission conforming to EN 55016-1-2
Conducted disturbance emission conforming to EN 55016-2-1