Main
Nominal input voltage
380...500 V AC three phase, terminal(s): L1, L2, L3
Power supply output current
40 A
anti-harmonic filter
Low frequency harmonic currents
Power supply type
Regulated switch mode
Complementary
output coupling
Parallel
Series
Product certifications
CCSAus
EAC
UL
RCM
Handle front plate colour
143 mm
power factor
0.85 at 24 V DC
Product or component type
Power supply
inrush current
25 A
Connections - terminals
Removable screw terminal block: 2 x 2.5 mm², for diagnostic relay
Screw type terminals: 3 x 0.5...3 x 4 mm², (AWG 22...AWG 12) for input connection
Screw type terminals: 1 x 0.5...1 x 4 mm², (AWG 22...AWG 12) for input ground connection
Screw type terminals: 4 x 0.5...4 x 10 mm², (AWG 22...AWG 8) for output connection
Efficiency
92 %
marking
CE
output voltage
24 V DC
width (w)
166 mm
input voltage limits
320...550 V AC
Net weight
2.7 kg
Operating position
Vertical
Mounting support
35 x 7.5 mm symmetrical DIN rail
35 x 15 mm symmetrical DIN rail
depth
160 mm
power dissipation in w
76.8 W
Permissible temporary current boost
1.5 x In (for 4 s)
output voltage adjustment
24...28.8 V adjustable
Rated power in w
960 W
Provided equipment
Power factor correction filter conforming to IEC 61000-3-2
dielectric strength
3500 V with between input and ground
4000 V with between input and output
500 V with between output and ground
output protection type
Against overload, protection technology: manual or automatic reset
Against overvoltage, protection technology: 30...32 V, manual reset
Against short-circuits, protection technology: manual or automatic reset
Against undervoltage, protection technology: tripping if U < 21.6 V
Thermal, protection technology: automatic reset
Status led
1 LED (green and red) output voltage
1 LED (green, red and orange) output current
Supply
SELV conforming to EN/IEC 60950-1
SELV conforming to EN/IEC 60204-1
SELV conforming to IEC 60364-4-41
Environment
ip degree of protection
IP20 conforming to EN/IEC 60529
operating altitude
2000 m
Range of product
Modicon Power Supply
ambient air temperature for operation
50…60 °C with derating factor mounting position A < 2000 m
-25…50 °C without derating mounting position A < 2000 m
Environmental characteristics
EMC conforming to EN 61000-6-1
EMC conforming to EN 61000-6-3
EMC conforming to EN 55024
EMC conforming to EN/IEC 61000-6-4
EMC conforming to EN/IEC 61204-3
Safety conforming to EN 61204-4
Safety conforming to EN/IEC 60950-1
standards
CSA C22.2 No 60950-1
UL 508
EN/IEC 62368-1