Complementary
maximum output current
40 A
output coupling
Parallel
Product certifications
EAC
RCM
mtbf reliability
2488391 H at 24 V DC with UTE C80-810 calculation method
Product or component type
Redundancy module
Connections - terminals
For output connection: screw type terminals, connection capacity: 2 x 0.5...2 x 10 mm² AWG 20...AWG 8
For input connection: screw type terminals, connection capacity: 4 x 0.5...4 x 10 mm² AWG 20...AWG 8
For diagnostic relay: removable screw terminal block, connection capacity: 1 x 2.5 mm² AWG 14
marking
CE
Fixing mode
By clips on 35 mm symmetrical DIN rail, operating position: horizontal
By clips on 35 mm symmetrical DIN rail, operating position: vertical
input current
20 A
output voltage
(Uin-0.2) V DC
input voltage limits
22...30 V
Local signalling
1 LED per input (green) for power supply status
1 relay for power supply status
Net weight
0.7 kg
Name of test
Electrostatic discharges conforming to EN/IEC 61000-4-2
Emission conforming to EN 61000-6-3
Induced electromagnetic field conforming to EN/IEC 61000-4-6 level 3
Radiated electromagnetic field conforming to EN/IEC 61000-4-3 level 3
Rapid transient conforming to IEC 61000-4-4 level 3
Surge conforming to EN/IEC 61000-4-5 level 2
Conducted/radiated emissions conforming to EN 55022 class B
Emission conforming to EN 50081-1
Number of output channels
1
input voltage
24...28.8 V DC
dielectric strength
500 V between input and ground
500 V between output and ground
output protection type
Against overload, protection technology: external protection by power supply
Against short-circuits, protection technology: external protection by power supply
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP20 conforming to EN/IEC 60529
operating altitude
2000 m
Range of product
Phaseo
ambient air temperature for operation
-25…60 °C
Environmental characteristics
EMC conforming to EN 61000-6-3
EMC conforming to EN/IEC 61000-6-2
Safety conforming to EN/IEC 60950-1
Safety conforming to EN/IEC 61204
overvoltage category
Class II conforming to VDE 0106-1
standards
CSA C22.2 No 60950-1
UL 508
relative humidity
0…90 % during operation
0…95 % during storage
vibration resistance
2 gn (f= 11.9…150 Hz) conforming to EN/IEC 61131-2
3.5 mm (f= 3…11.9 Hz) conforming to EN/IEC 61131-2