Main
power supply module output current
0,6 A
product range
Alimentation Modicon
type of product or equipment
Alimentation puissance
nominal power in w
15 W
rated input voltage
100...240 V CA phase-phase, raccordement(s): L1-L2
100...240 V CA monophasé, raccordement(s): N-L1
120...250 V CC
kind of power supply
Mode commutation régulée
Complementary
18 mm pitches
0.5 at 24 V DC
feed
SELV se conformer à EN/CEI 60950-1
SELV se conformer à EN/CEI 60204-1
SELV se conformer à CEI 60364-4-41
power consumption
0,25 A 240 V CA
0,4 A 100 V CA
output coupling
Parallèle
Séries
Handle front plate colour
100 mm
inrush current
20 A
product weight
0,1 kg
marking
CE
led status
1 LED (vert) tension de sortie
connection mode
Bornes de type vis: 2 x 0,14 à 2 x 2,5 mm², (AWG 26…AWG 14) pour connexion entrée
Bornes de type vis: 2 x 0,14 à 2 x 2,5 mm², (AWG 26…AWG 14) pour connexion sortie
output voltage
24 V CC
width (w)
36 mm
input voltage limits
85...264 V CA
residual ripple
250 mV
depth
59 mm
mounting bracket
profilé symétrique 35x7,5mm
panneau à 2 vis, diamètre : 4 mm
profilé symétrique 35x15mm
power dissipation in w
3,8 W
yield
80 %
output voltage adjustment
Réglable de 22,8 à 28,8 V
mounting position
Verticale
dielectric strength
3000 V avec entre entrée et sortie
output protection type
Thermique
Contre les courts-circuits
input protection type
Fusible intégré (non interchangeable)
Environment
environment characteristic
CEM se conformer à EN 55022 Class B
CEM se conformer à EN 61000-6-3
CEM se conformer à EN/CEI 61000-6-2
CEM se conformer à EN/CEI 61204-3
Sécurité se conformer à EN/CEI 60950-1
ip degree of protection
IP20 se conformer à EN/CEI 60529
operating altitude
2000 m
product certificates
TUV 60950-1
EAC
KC
RCM
CCSAus
CSA 22-2 No 950
CULus 508
ambient air temperature for operation
-25…55 °C sans déclassement mounting position A < 2000 m
55…70 °C avec facteur de réduction mounting position A < 2000 m
standards
UL 508
CSA C22.2 No 60950-1
EN/CEI 62368-1