Main
Nominal input voltage
230 V AC single phase, terminal(s): N-L1
400 V AC phase to phase, terminal(s): L1-L2
Power supply output current
4 A
anti-harmonic filter
Low frequency harmonic currents
Power supply type
Rectified and filtered
Complementary
compatibility code
ABL8F
output coupling
Series
Parallel
Product certifications
cULus
KC
UL 508
EAC
Handle front plate colour
108 mm
power factor
0.689 at 230 V
0.867 at 400 V
Product or component type
Power supply
Connections - terminals
For input connection: screw type terminals, connection capacity: 5 x 2.5...5 x 4 mm² AWG 14...AWG 11
For input ground connection: screw type terminals, connection capacity: 1 x 2.5...1 x 4 mm² AWG 14...AWG 11
For output connection: screw type terminals, connection capacity: 4 x 2.5...4 x 4 mm² AWG 14...AWG 11
Efficiency
75 %
network frequency limits
47…63 Hz
Hold-up time
14 ms
output voltage
24 V DC
width (w)
87 mm
input voltage limits
360...440 V
207...253 V
Net weight
2.98 kg
residual ripple
<= 1200 MV
depth
164.0 mm
power dissipation in w
24 W
Rated power in w
96 W
dielectric strength
2000 V between input and ground
4600 V between input and output
500 V between output and ground
output protection type
Against overload and short-circuits, protection technology: internal fuse, 4 A, 5 x 20 mm, T curve
Against overvoltage, protection technology: 2 J peak limiter
Status led
1 LED (green) output voltage
1 LED (orange) input voltage
Environment
Ambient air temp for storage/transportation
-40…80 °C
ip degree of protection
IP20 conforming to EN/IEC 60529
operating altitude
3000 m
Range of product
Modicon Rectified
ambient air temperature for operation
-20…60 °C
other environmental characteristic
EMC conforming to IEC 62041
Safety conforming to EN/IEC 61558-2-6
Safety conforming to UL 508
Safety conforming to UL 60950-1
EMC conforming to EN/IEC 61000-3-2
relative humidity
0…95 % without condensation or dripping water
Safety class
Class I conforming to VDE 0106-1
vibration resistance
0.05 mm (f= 47…57 Hz) conforming to IEC 60068-1
0.7 gn (f= 13.9…47 Hz) conforming to IEC 60068-1
1 gn (f= 57…150 Hz) conforming to IEC 60068-1
1 mm (f= 3…13.9 Hz) conforming to IEC 60068-1