Complementary
Activation threshold
(Uin-1) V and 22 V min
maximum output current
40 A
output coupling
Parallel
Product certifications
RCM
EAC
Charging time
25 s
mtbf reliability
1119603 H at 24 V DC with UTE C80-810 calculation method
Product or component type
Buffer module
Current consumption
0.6 A on load
0.1 mA no load
<= 40.6 A
Connections - terminals
For input connection: screw type terminals, connection capacity: 2 x 0.5...2 x 10 mm² AWG 20...AWG 8
For output connection: screw type terminals, connection capacity: 2 x 0.5...2 x 10 mm² AWG 20...AWG 8
For diagnostic relay: removable screw terminal block, connection capacity: 1 x 2.5 mm² AWG 14
marking
CE
maximum power dissipation in w
15 W
Fixing mode
By clips on 35 mm symmetrical DIN rail, operating position: horizontal
By clips on 35 mm symmetrical DIN rail, operating position: vertical
output voltage
(Uin-0.25) V in nominal mode DC
(Uin-1) V in buffer mode DC
input voltage limits
22...30 V
Local signalling
1 LED (green) for buffer ready
1 relay for buffer ready
Net weight
1.2 kg
holding time
0.1 s at 40 A
6 s at 0.5 A
Name of test
Electrostatic discharges conforming to EN/IEC 61000-4-2
Emission conforming to EN 61000-6-3
Induced electromagnetic field conforming to EN/IEC 61000-4-6 level 3
Radiated electromagnetic field conforming to EN/IEC 61000-4-3 level 3
Rapid transient conforming to IEC 61000-4-4 level 3
Surge conforming to EN/IEC 61000-4-5 level 2
Conducted/radiated emissions conforming to EN 55022 class B, 20 %
Number of output channels
1
input voltage
24...28.8 V DC
dielectric strength
500 V between input and ground
500 V between output and ground
output protection type
Against overload, protection technology: > 45 A
Against short-circuits, protection technology: power-supplied mode, automatic reset
Against undervoltage, protection technology: tripping if U < 19 V
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP20 conforming to EN/IEC 60529
operating altitude
2000 m
Range of product
Phaseo
ambient air temperature for operation
-25…60 °C
Environmental characteristics
EMC conforming to EN 61000-6-3
EMC conforming to EN/IEC 61000-6-2
Safety conforming to EN/IEC 60950-1
Safety conforming to EN/IEC 61204-3
overvoltage category
Class II conforming to VDE 0106-1
standards
UL 508
CSA C22.2 No 60950-1
relative humidity
0…90 % during operation
0…95 % during storage
vibration resistance
2 gn (f= 11.9…150 Hz) conforming to EN/IEC 61131-2
3.5 mm (f= 3…11.9 Hz) conforming to EN/IEC 61131-2