All categories
Compare Cart

ABL6TS40G - Voltage transformer 230..400 V 1 x 115 V 400 VA - Schneider Electric

Expected in 2-4 weeks
ABL6TS40G - Voltage transformer 230..400 V 1 x 115 V 400 VA - Schneider Electric - Voltage transformer 230..400 V 1 x 115 V 400 VA - Schneider Electric - 0
ABL6TS40G - Voltage transformer 230..400 V 1 x 115 V 400 VA - Schneider Electric
251,36 €
251,36 € incl. VAT
Text About:
Voltage transformer 230..400 V 1 x 115 V 400 VA - Schneider Electric
251,36 €
SPECIFICATIONS
Main
secondary winding Single
Complementary
electrical insulation class Class B
Product certifications UR
EAC
DNV-GL
Handle front plate colour 108.0 mm
Product or component type Safety and isolation transformer
Connections - terminals For input connection: screw type terminals, connection capacity: 5 x 4 mm² AWG 11
For input ground connection: screw type terminals, connection capacity: 1 x 4 mm² AWG 11
For output connection: screw type terminals, connection capacity: 2 x 4 mm² AWG 11
Efficiency 92 %
rated power in va 400 VA
marking CE
network frequency limits 47…63 Hz
Fixing mode By 4 screws diameter: 5.8 mm on vertical panel, operating position: horizontal
By 4 screws diameter: 5.8 mm on vertical panel, operating position: vertical
By 4 screws diameter: 5.8 mm on horizontal panel with derating to 90 %
output voltage 115 V AC
width (w) 135.0 mm
input voltage limits 360...440 V
207...253 V
Net weight 6.25 kg
Maximum voltage drop at rated load 0.5 %
depth 134.0 mm
power dissipation in w 34.8 W
input voltage tolerance +/- 15 V
No load losses 12.4 W
input voltage 230 V AC single phase, terminal(s): N-L1
400 V AC phase to phase, terminal(s): L1-L2
Output sustained overvoltage 4 % (no load, hot state)
dielectric strength 2000 V between winding and ground
4000 V between primary and secondary
output protection type Against overload, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection
Against overvoltage, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection
Against short-circuits, protection technology: with additional protection fuses or circuit-breakers in Selection of Protection
Protective cover Without
Short-circuit voltage 0,0466
Environment
Ambient air temp for storage/transportation -40…80 °C
ip degree of protection IP20
operating altitude 3000 m
Range of product Modicon Transformer Optimized
ambient air temperature for operation -20…50 °C
Environmental characteristics EMC conforming to EN 62041
Safety conforming to EN 61558-1
Safety conforming to EN 61558-2-4
overvoltage category Class I conforming to VDE 0106-1
standards UL 506
protective treatment TC
Recently viewed
251,36 €
251,36 € incl. VAT
Expected in 2-4 weeks