Main
Device short name
iID
Range
Acti9
Earth-leakage protection class
Type A
Neutral position
Left
Earth-leakage protection time delay
Instantaneous
Earth-leakage sensitivity
100 mA
Product Name
Acti9 iID
[ui] rated insulation voltage
500 V AC 50/60 Hz
Complementary
9 mm pitches
4
[in] rated current
40 A
[ue] rated operational voltage
220...240 V AC 50/60 Hz
[ics] rated service breaking capacity
Idm 1500 A
Im 1500 A
Control type
Toggle
Handle front plate colour
91 mm
Product or component type
Residual current circuit breaker (RCCB)
tightening torque
3.5 N.m top or bottom
[uimp] rated impulse withstand voltage
6 kV
Connections - terminals
Double terminal front 1…35 mm² rigid
Double terminal front 1…25 mm² flexible
Double terminal front 1…25 mm² flexible with ferrule
Double terminal back 1…25 mm² rigid
Double terminal back 1…16 mm² flexible
Double terminal back 1…16 mm² flexible with ferrule
Locking options description
Padlocking device
Contact position indication
Yes
width (w)
36 mm
network frequency
50/60 Hz
Colour
White
Mounting mode
Clip-on
Net weight
0.21 kg
wire stripping length
14 mm for top or bottom connection
Mounting support
DIN rail
depth
73 mm
mechanical durability
20000 cycles
electrical durability
AC-1: 15000 cycles
Network type
AC
Pollution degree
3
residual current tripping technology
Voltage independent
Rated conditional short-circuit current
10 kA
Poles description
2P
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529
ambient air temperature for operation
-25…60 °C
electromagnetic compatibility
8/20 µs impulse withstand, 250 A conforming to EN/IEC 61008-1
standards
EN/IEC 61008-1
EN/IEC 61008-2-1