Main
Device short name
ID K
Device location in system
Outgoer
Range
Acti9
Earth-leakage protection class
Type A
Neutral position
Left
Earth-leakage protection time delay
Instantaneous
Earth-leakage sensitivity
30 mA
Product Name
Acti9 ID K
[ui] rated insulation voltage
440 V AC 50 Hz
Complementary
9 mm pitches
4
[in] rated current
25 A
[ue] rated operational voltage
220...240 V AC 50 Hz
[ics] rated service breaking capacity
Idm 500 A
Im 500 A
Control type
Toggle
Handle front plate colour
81 mm
Product or component type
Residual current circuit breaker (RCCB)
tightening torque
3.5 N.m top or bottom
[uimp] rated impulse withstand voltage
4 kV
Connections - terminals
Biconnect top or bottom 1…35 mm² rigid
Biconnect top or bottom 1…25 mm² flexible
Contact position indication
No
width (w)
36 mm
network frequency
50/60 Hz
Colour
White
Mounting mode
Clip-on
Net weight
0.18 kg
wire stripping length
14 mm for top or bottom connection
Mounting support
DIN rail
depth
68 mm
mechanical durability
5000 cycles
electrical durability
AC-1: 2000 cycles
Network type
AC
Pollution degree
2
residual current tripping technology
Voltage independent
Surge current
250 A
Rated conditional short-circuit current
GL63: Inc 4.5 kA
K60: Inc 6 kA
Poles description
2P
Environment
Ambient air temp for storage/transportation
-30…70 °C
ip degree of protection
IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529
ambient air temperature for operation
-25…40 °C
electromagnetic compatibility
8/20 µs impulse withstand, 200 A conforming to EN/IEC 61008-1
standards
EN/IEC 61008-1
EN/IEC 61008-2-1
quality labels
VDE