Main
Range
Acti9
name of the device
Vigi iTG40
type of product or equipment
Blocs différentiels Vigi
differential sensitivity
30 mA
[ui] rated insulation voltage
400 V CA 50 Hz se conformer à EN/CEI 61009-2-1
neutral pole position
Gauche
Complementary
9 mm pitches
2
[ue] rated operational voltage
230 V CA 50 Hz
range compatibility
Acti9 (Acti9 iDT40)
electrical connection on circuit breaker
Par vis
Handle front plate colour
91 mm
tightening torque
2 N.m haut
[uimp] rated impulse withstand voltage
4 kV se conformer à EN/CEI 61009-2-1
in rated operational current
40 A
mode d'installation
Encliquetable
electrical life
10000 cycle
connection mode
Borne du type à cage haut1…16 mm² rigide
Borne du type à cage haut1…10 mm² souple
mechanical endurance
20000 cycle
width (w)
36 mm
network frequency
50 Hz
Colour
Blanc
delay
Instantané
voltage indication
Signalisation de défaut
position of the switchgear in the installation
Groupe d'arrivées
wire stripping length
14 mm pour haut connexion
depth
74 mm
differential technology
Indépendant de la tension
mounting bracket
Rail DIN
Network type
Type AC
Poles description
1P + N
Environment
degree of pollution
3 se conformer à EN/CEI 61009-2-1
ip degree of protection
IP20 conforming to CEI 60529
IP40 (boîtier modulaire) conforming to CEI 60529
operating altitude
2000 m
product certificates
CE
standards
EN/CEI 61009-2-1
quality labels
NF
relative humidity
95 % à 55 °C
operating temperature
-5…60 °C
storage room temperature
-40…85 °C