Device short name
Vigi iC60
Device location in system
Outgoer
Range
Acti9
Earth-leakage protection time delay
Instantaneous
Earth-leakage sensitivity
300 mA
[ui] rated insulation voltage
500 V AC 50/60 Hz conforming to IEC 60947-2
earth leakage protection type
Type A
Complementary
9 mm pitches
6
product compatibility
Single terminal
[in] rated current
25 A
[ue] rated operational voltage
400 V AC 50/60 Hz conforming to EN 61009-1
400/415 V AC 50/60 Hz conforming to IEC 61009-1
conforming to IEC/EN 61009-2-1
range compatibility
Acti 9 (Acti9 iC60)
Acti 9 (Acti9 Reflex iC60)
Handle front plate colour
91 mm
Product or component type
Add-on residual current devices
tightening torque
2 N.m bottom
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-2
Comb busbar and distribution block compatibility
Bottom: YES
Connections - terminals
Tunnel type terminal downside for 1 cable(s) 1…25 mm² rigid without cable end
Tunnel type terminal downside for 1 cable(s) 1…16 mm² flexible without cable end
Tunnel type terminal downside for 1 cable(s) 1…16 mm² flexible with cable end
Electrical connection to mcb
By screws
width (w)
54 mm
network frequency
50/60 Hz
Local signalling
Trip indicator
Mounting mode
Clip-on
Net weight
0.21 kg
wire stripping length
14 mm for bottom connection
Mounting support
DIN rail
depth
73.5 mm
Network type
AC
Pollution degree
3 conforming to IEC 60947-2
residual current tripping technology
Voltage independent
Poles description
3P
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529
ambient air temperature for operation
-25…60 °C
electromagnetic compatibility
8/20 µs impulse withstand, 250 A conforming to IEC 61009-1
standards
EN 61009-1