SPECIFICATIONS
Main
Range Acti9
name of the device iID
type of product or equipment Interrupteur différentiel
differential sensitivity 300 mA
Product Name Acti 9 iID
[ui] rated insulation voltage 500 V CA 50/60 Hz
neutral pole position Gauche
Complementary
9 mm pitches 4
[ue] rated operational voltage 220...240 V CA 50/60 Hz
peak current 250 A
[ics] rated service breaking capacity Idm 1500 A
Im 1500 A
Handle front plate colour 91 mm
tightening torque 3,5 N.m haut ou bas
[uimp] rated impulse withstand voltage 6 kV
in rated operational current 25 A
product weight 0,21 kg
fully apparent cut Oui
mode d'installation Encliquetable
electrical life AC-1: 15000 cycle
connection mode Terminal simple haut ou bas1…35 mm² rigide
Terminal simple haut ou bas1…25 mm² souple
Terminal simple haut ou bas1…25 mm² flexible avec embout
mechanical endurance 20000 cycle
width (w) 36 mm
network frequency 50/60 Hz
Colour Blanc
delay Instantané
nominal conditional short-circuit current 10 kA
position of the switchgear in the installation Départ
wire stripping length 14 mm pour haut ou bas connexion
depth 73,5 mm
differential technology Indépendant de la tension
mounting bracket Rail DIN
Network type Type AC
optional locks Dispositif de cadenassage
order type Par maneton
Poles description 2P
Environment
degree of pollution 3
ip degree of protection IP20 conforming to CEI 60529
IP40 (boîtier modulaire) conforming to CEI 60529
electromagnetic compatibility Tenue aux ondes 8/20 µs, 250 A se conformer à EN/CEI 61008-1
standards EN/CEI 61008-1
operating temperature -5…60 °C
storage room temperature -40…85 °C