Additional Information
curve
C
Main
Device short name
iC40N
Range
Acti9
Neutral position
Left
Number of protected poles
1
Product Name
Acti9 iC40
Trip unit technology
Thermal-magnetic
[ui] rated insulation voltage
400 V AC 50/60 Hz conforming to EN/IEC 60947-2
Complementary
9 mm pitches
2
[in] rated current
16 A
[ue] rated operational voltage
230 V AC 50/60 Hz
[ics] rated service breaking capacity
6000 A 100 % x Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
7.5 kA 75 % x Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60947-2
Control type
Toggle
Product certifications
CE
BV
RINA
DNV
Handle front plate colour
85 mm
Product or component type
Miniature circuit-breaker
tightening torque
2 N.m top or bottom
[uimp] rated impulse withstand voltage
4 kV conforming to EN/IEC 60947-2
Connections - terminals
Tunnel type terminals top or bottom 1…10 mm² flexible
Tunnel type terminals top or bottom 1…16 mm² rigid
Locking options description
Padlocking device
Contact position indication
Yes
Device application
Distribution
width (w)
18 mm
network frequency
50/60 Hz
Colour
White
Local signalling
ON/OFF indication
Trip indicator
Mounting mode
Clip-on
Net weight
120 g
wire stripping length
14 mm for top or bottom connection
Earth-leakage protection
Separate block
Mounting support
DIN rail
depth
74 mm
mechanical durability
20000 cycles
electrical durability
20000 cycles
magnetic trip limit
5...10 x In conforming to EN/IEC 60898-1
8 x In +/- 20 % conforming to EN/IEC 60947-2
Network type
AC
Pollution degree
3 conforming to EN/IEC 60947-2
Limitation class
3 conforming to EN/IEC 60898-1
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Poles description
1P + N
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529
operating altitude
2000 m
ambient air temperature for operation
-25…70 °C
standards
EN/IEC 60898-1
EN/IEC 60947-2
quality labels
RCM
AENOR
IMQ
OVE
relative humidity
95 % at 55 °C