Additional Information
curve
B
Main
Device short name
C60PV-DC
Number of protected poles
2
[ui] rated insulation voltage
1000 V DC
Complementary
9 mm pitches
8
[in] rated current
8 A
[ue] rated operational voltage
800 V DC
compatibility code
C60PV-DC
[ics] rated service breaking capacity
1.5 kA 100 % - 800 V DC
3 kA 100 % - 650 V DC
Control type
Toggle
Handle front plate colour
132.7 mm
Product or component type
Miniature circuit-breaker
tightening torque
2.5 N.m
[uimp] rated impulse withstand voltage
6 kV
Connections - terminals
Tunnel terminal (downside) 1…25 mm² rigid
Tunnel terminal (downside) 1…16 mm² flexible
Pre-wired cable (upside)
Locking options description
Padlocking in OFF position
Contact position indication
Yes
width (w)
72 mm
Colour
White
Mounting mode
Fixed
Net weight
0.545 kg
wire stripping length
14 mm
Mounting support
35 mm symmetrical DIN rail
depth
77.4 mm
mechanical durability
20000 cycles
electrical durability
1500 cycles L/R = 2 ms
magnetic trip limit
5.5 x In
Network type
DC
Pollution degree
2
Voltage drop
1384 mV 173 mOhm 11.1 W 8 A
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Poles description
2P
Utilisation category
Category A conforming to EN/IEC 60947-2
Environment
Ambient air temp for storage/transportation
-40…85 °C
Range of product
C60
ambient air temperature for operation
-25…70 °C
standards
EN/IEC 60947-2
relative humidity
95 % at 55 °C